| 2019-07-25 08:31:18 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS THAT WERE SUBMITTED HAVE A COPIED |
| | SIGNATURE AND SEAL OF A FLORIDA LICENSED ARCHITECT IN |
| | THE TITLE BLOCK. THE PLANS ARE REQUIRED TO HAVE THE |
| | ARCHITECT'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL. |
| | 61G1-16.003 USE OF SEAL. (1) THE PERSONAL SEAL, |
| | SIGNATURE AND DATE OF THE ARCHITECT OR INTERIOR |
| | DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR INTERIOR |
| | DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND |
| | SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS |
| | CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT. |
| | DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE |
| | RESPONSIBLE ARCHITECT OR INTERIOR DESIGNER. FINAL |
| | OFFICIAL RECORD DOCUMENTS (NOT TRACINGS, ETC.) SHALL BE |
| | SO SIGNED. THE SIGNING AND SEALING OF THE SPECIFICATION |
| | INDEX SHEETS SHALL BE CONSIDERED ADEQUATE. ALL DRAWING |
| | SHEETS AND PAGES SHALL BE SO SIGNED AND SEALED. AN |
| | ARCHITECT OR INTERIOR DESIGNER SHALL NOT AFFIX, OR |
| | PERMIT TO BE AFFIXED, HIS SEAL OR NAME TO ANY PLAN, |
| | SPECIFICATIONS, DRAWINGS, OR OTHER RELATED DOCUMENT |
| | WHICH WAS NOT PREPARED BY HIM OR UNDER HIS RESPONSIBLE |
| | SUPERVISING CONTROL AS PROVIDED IN RULE CHAPTER |
| | 61G1-23, F.A.C. AN ARCHITECT OR INTERIOR DESIGNER SHALL |
| | NOT USE HIS SEAL OR DO ANY OTHER ACT AS AN ARCHITECT OR |
| | INTERIOR DESIGNER UNLESS HOLDING AT THE TIME A |
| | CERTIFICATE OF REGISTRATION AND ALL REQUIRED RENEWALS |
| | THEREOF. |
| | (2) WHEN UTILIZING ELECTRONICALLY TRANSMITTED PLANS, |
| | WHICH ARE DIGITALLY SIGNED AND SEALED PURSUANT TO THE |
| | PROVISIONS OF RULE 61G1-16.005, F.A.C., AND WHEN ALL |
| | THE TRANSMITTED DRAWINGS ARE TRANSMITTED AS A |
| | SINGLE-BOUND AND SECURED SET, IT SHALL BE SUFFICIENT |
| | FOR THE ARCHITECT OR INTERIOR DESIGNER TO APPLY THEIR |
| | DIGITAL SIGNATURE AND SEAL TO THE COVER OR FIRST SHEET |
| | OF THAT BOUND SET, AS LONG AS AN ACCURATE INDEX OF |
| | DRAWINGS, LISTING ALL THE ARCHITECTURAL OR INTERIOR |
| | DESIGN SHEETS, WITH THEIR SHEET NUMBER AND LATEST |
| | REVISE DATE, WHICH ARE INTENDED TO BE SIGNED AND SEALED |
| | IS INCLUDED WITHIN THAT COVER OR FIRST SHEET. |
| | |
| | 2) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, |
| | ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO |
| | PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS |
| | WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID |
| | RECEIPT MUST BE RETURNED TO THE CITY BUILDING |
| | DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED. |
| | FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT |
| | (561) 233-5025. |
| | |
| | 4) PROVIDE A BOND BREAK BETWEEN THE WATER RESISTIVE |
| | BARRIER AND THE STUCCO. R703.7.3 WATER-RESISTIVE |
| | BARRIERS. |
| | WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| | IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED |
| | SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| | VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| | EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| | INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| | THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| | AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| | R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| | BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| | EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT IS |
| | APPLIED OVER WOOD-BASED SHEATHING HAS A WATER |
| | RESISTANCE EQUAL TO OR GREATER THAN THAT OF 60-MINUTE |
| | GRADE D PAPER AND IS SEPARATED FROM THE STUCCO BY AN |
| | INTERVENING, SUBSTANTIALLY NON-WATER-ABSORBING LAYER OR |
| | DESIGNED DRAINAGE SPACE. |
| | |
| | 5) A WEEP SCREED IS REQUIRED AT THE BOTTOM OF THE WOOD |
| | FRAME AND STUCCO WALLS. R703.7.2.1 WEEP SCREEDS. |
| | A MINIMUM 0.019-INCH (0.5 MM) (NO. 26 GALVANIZED SHEET |
| | GAGE), CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP |
| | SCREED, WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF |
| | 31/2 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE |
| | FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN |
| | ACCORDANCE WITH ASTM C926. THE WEEP SCREED SHALL BE |
| | PLACED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE EARTH |
| | OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A |
| | TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE |
| | EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER |
| | SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH |
| | SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF |
| | THE WEEP SCREED. |
| | |
| | |
| | RE-SUBMITTAL PROCEDURE |
| | YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE |
| | SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER |
| | DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED |
| | APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE |
| | REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN |
| | CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK |
| | WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER. |
| | ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED |
| | SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH |
| | THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED |
| | SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED |
| | FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS, |
| | RESUBMIT THOSE SHEETS. |
| | IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| | (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS |
| | SHALL BE SUBMITTED. |
| | |
| | |