| Plan Review Notes For Permit 19061433 |
| Permit Number |
19061433 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-08-29 14:41:35 | 1) THE PUMP CURVE AND PRINTING THAT IS ON SHT. 3 0F 4 | | | IS ILLEGIBLE.SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP | | | CURVE. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS | | | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS | | | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE | | | TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, | | | 4.4.9.1. | | | 2) GAS FIRED POOL HEATERS SHALL HAVE A MINIMUM THERMAL | | | EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. | | | R403.10.4. THE SUBMITTED SPECS DO NOT SHOW THIS. |
|