| Plan Review Notes For Permit 19061433 |
| Permit Number |
19061433 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-08-13 09:47:02 | 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS | | | FOR THE POOL HEATER THAT SHOWS THE HEATER HAS A THERMAL | | | EFFICIENCY OF AT LEAST 82% PER THE 2017 FBC- ENERGY | | | SEC.R403.10.4. | | | 2) SUBMIT TWO COPIES OF AN ENLARGED POOL PUMP CURVE. | | | THE PRINTING IS ILLEGIBLE ON THE PLANS. IDENTIFY ON THE | | | PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP | | | BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM | | | THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS. | | | 3) SUBMIT LEGIBLE TOTAL DYNAMIC HEAD CALCULATIONS. THE | | | PRINTING IS BARELY LEGIBLE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|