Plan Review Notes
Plan Review Notes For Permit 19061433
Permit Number 19061433
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-13 09:47:021) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 FOR THE POOL HEATER THAT SHOWS THE HEATER HAS A THERMAL
 EFFICIENCY OF AT LEAST 82% PER THE 2017 FBC- ENERGY
 SEC.R403.10.4.
 2) SUBMIT TWO COPIES OF AN ENLARGED POOL PUMP CURVE.
 THE PRINTING IS ILLEGIBLE ON THE PLANS. IDENTIFY ON THE
 PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP
 BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM
 THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS.
 3) SUBMIT LEGIBLE TOTAL DYNAMIC HEAD CALCULATIONS. THE
 PRINTING IS BARELY LEGIBLE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW