2019-09-17 16:36:05GAS 2ND REVIEW**DENIED**
  
 1) SHOW TYPE OF PIPING BEING USED ON ISOMETRIC DRAWING.
 SHT. P0.1 IN THE NOTES CALL OUT BLACK IRON UNDER
 GROUND. BLACK IRON IS PERMITTED UNDERGROUND WITH
 COATINGS APPLIED. FBC-GAS 404.11, 404.11.2. SHOW THE
 TYPE OF PIPE MATERIAL BEING INSTALLED, ALL PIPE SIZES,
 AND THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING. (IF APPLICABLE) FOR EACH PIPE
 SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37)
  
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2,
  
  