| 2019-07-25 17:52:46 | 1ST REVIEW: 19061420 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE FLOOR DRAIN THAT IS LOCATED IN FRONT OF THE |
| | THREE COMPARTMENT SINK SHALL BE CONNECTED TO THE INLET |
| | SIDE OF THE GREASE INTERCEPTOR . PER FBC PL 1003.3.1 |
| | |
| | 2. HORIZONTAL DRY VENTS ARE PROHIBITED THEY ARE SHOWN |
| | ON THE TOILETS, GREASE INTERCEPTOR, THE FLOOR SINK IN |
| | FRONT OF THE GRIDDLE, THE HUB DRAIN IN FRONT OF THE |
| | FREEZER, THE FLOOR DRAIN IN FRONT OF THE SINGLE |
| | COMPARTMENT SINK AND THREE COMPARTMENT SINK, THE FLOOR |
| | SINK UNDER THE 3 COMPARTMENT SINK THE VENT SHALL COME |
| | OFF THE TOP OF THE PIPE INTO A WALL. PER FBC PL 905.3 + |
| | 4 |
| | |
| | 3.PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR |
| | GREASE INTERCEPTOR BY SCHIER. PER WPB AMEND TO FBC |
| | 107.2.1 AND FBC PL 1003.2 |
| | |
| | 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND |
| | INSTALLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. A SAMPLING POINT IS REQUIRED ON THE OUTLET SIDE OF |
| | THE GREASE INTERCEPTOR PROVIDE PIPING DETAIL . PER WPB |
| | UTILITIES DEPT |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |