| Date |
Text |
| 2019-07-25 17:48:39 | 1ST REVIEW: 19061420 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO |
| | THE TOP OF THE GRIPPING SURFACE PLACE NOT ON PLAN OR |
| | SHOW ON DETAILS. PER FBC ACC 609.4 |
| | |
| | 2. THE FLOOR DRAIN THAT IS LOCATED IN FRONT OF THE |
| | THREE COMPARTMENT SINK SHALL BE CONNECTED TO THE INLET |
| | SIDE OF THE GREASE INTERCEPTOR . PER FBC PL 1003.3.1 |
| | |
| | 3. HORIZONTAL DRY VENTS ARE PROHIBITED THEY ARE SHOWN |
| | ON THE TOILETS, THE FLOOR SINK IN FRONT OF THE GRIDDLE, |
| | THE HUB DRAIN IN FRONT OF THE FREEZER, THE FLOOR DRAIN |
| | IN FRONT OF THE SINGLE COMPARTMENT SINK AND THREE |
| | COMPARTMENT SINK, THE FLOOR SINK UNDER THE 3 |
| | COMPARTMENT SINK THE VENT SHALL COME OFF THE TOP OF THE |
| | PIPE INTO A WALL. PER FBC PL 905.3 + 4 |
| | |
| | 4. A BACKFLOW IS REQUIRED ON THE ICE MACHINE AND DRINK |
| | MACHINES. PER FBC PL 608.3, 608.16.1, 608.16.10 |
| | |
| | 5. SHOW RECERC LINE, AIR HAMMER ARRESTORS, SHUT OFF |
| | VALVES ON EACH DROP, LABEL HOT AND COLD SHOW DIRECTION |
| | OF FLOW, NOTE ON PLAN INSULATION REQUIRED ON HOT WATER |
| | RECIRCULATION LOOP ON THE WATER RISER.PER FBC PL |
| | 606.1(5), 604.9, E] 607.5 |
| | |
| | 6.PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR |
| | GREASE INTERCEPTOR BY SCHIER. PER WPB AMEND TO FBC |
| | 107.2.1 AND FBC PL 1003.2 |
| | |
| | 7. THE HAND SINK THAT IS SHOWN UPSTREAM OF THE BATHROOM |
| | GROUP SHALL CONNECT DOWN STREAM OF THE BATHROOM GROUP. |
| | PER FBC PL 912.1 |
| | |
| | 8. THE TOILETS SHALL CONNECT TO THE SAME BRANCH AS THE |
| | LAVATORY AND FLOOR DRAINS IN THE BATHROOMS BEING VENTED |
| | BY THE LAVATORY VENT. PER FBC PL 912.1 |
| | |
| | 9. A RPZ BACKFLOW IS REQUIRED ON THE COLD WATER TO |
| | SUPPLY PIPPING FEEDING THIS TENNENT SPACE IN ORDER TO |
| | ISOLATE IT FROM THE REST OF THE BUILDING UNLESS IT IS |
| | ON A SEPARATE METER WITH EXISTING BACKFLOW. PER FBC PL |
| | 608.1 |
| | |
| | 10. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND |
| | INSTALLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 11. A SAMPLING POINT IS REQUIRED ON THE OUTLET SIDE OF |
| | THE GREASE INTERCEPTOR PROVIDE PIPING DETAIL . PER WPB |
| | UTILITIES DEPT |
| | |
| | 12. PLACE NOTE ON FLOOR PLAN TEMPERED WATER SHALL BE |
| | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. PER FBC PL 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |