Plan Review Notes
Plan Review Notes For Permit 19061420
Permit Number 19061420
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-25 17:48:391ST REVIEW: 19061420
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE PLACE NOT ON PLAN OR
 SHOW ON DETAILS. PER FBC ACC 609.4
  
 2. THE FLOOR DRAIN THAT IS LOCATED IN FRONT OF THE
 THREE COMPARTMENT SINK SHALL BE CONNECTED TO THE INLET
 SIDE OF THE GREASE INTERCEPTOR . PER FBC PL 1003.3.1
  
 3. HORIZONTAL DRY VENTS ARE PROHIBITED THEY ARE SHOWN
 ON THE TOILETS, THE FLOOR SINK IN FRONT OF THE GRIDDLE,
 THE HUB DRAIN IN FRONT OF THE FREEZER, THE FLOOR DRAIN
 IN FRONT OF THE SINGLE COMPARTMENT SINK AND THREE
 COMPARTMENT SINK, THE FLOOR SINK UNDER THE 3
 COMPARTMENT SINK THE VENT SHALL COME OFF THE TOP OF THE
 PIPE INTO A WALL. PER FBC PL 905.3 + 4
  
 4. A BACKFLOW IS REQUIRED ON THE ICE MACHINE AND DRINK
 MACHINES. PER FBC PL 608.3, 608.16.1, 608.16.10
  
 5. SHOW RECERC LINE, AIR HAMMER ARRESTORS, SHUT OFF
 VALVES ON EACH DROP, LABEL HOT AND COLD SHOW DIRECTION
 OF FLOW, NOTE ON PLAN INSULATION REQUIRED ON HOT WATER
 RECIRCULATION LOOP ON THE WATER RISER.PER FBC PL
 606.1(5), 604.9, E] 607.5
  
 6.PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR
 GREASE INTERCEPTOR BY SCHIER. PER WPB AMEND TO FBC
 107.2.1 AND FBC PL 1003.2
  
 7. THE HAND SINK THAT IS SHOWN UPSTREAM OF THE BATHROOM
 GROUP SHALL CONNECT DOWN STREAM OF THE BATHROOM GROUP.
 PER FBC PL 912.1
  
 8. THE TOILETS SHALL CONNECT TO THE SAME BRANCH AS THE
 LAVATORY AND FLOOR DRAINS IN THE BATHROOMS BEING VENTED
 BY THE LAVATORY VENT. PER FBC PL 912.1
  
 9. A RPZ BACKFLOW IS REQUIRED ON THE COLD WATER TO
 SUPPLY PIPPING FEEDING THIS TENNENT SPACE IN ORDER TO
 ISOLATE IT FROM THE REST OF THE BUILDING UNLESS IT IS
 ON A SEPARATE METER WITH EXISTING BACKFLOW. PER FBC PL
 608.1
  
 10. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB
 AMEND TO FBC 107.2.1
  
 11. A SAMPLING POINT IS REQUIRED ON THE OUTLET SIDE OF
 THE GREASE INTERCEPTOR PROVIDE PIPING DETAIL . PER WPB
 UTILITIES DEPT
  
 12. PLACE NOTE ON FLOOR PLAN TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]