| Date |
Text |
| 2019-07-25 18:20:17 | 1ST REVIEW: 19091420 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) & 2017 FUEL GAS CODE |
| | SEC. 402.4.1. A NOTE ON THE FLOOR PLAN LIST 200' THE |
| | GAS LOAD SUMMARY LIST 150' PLEASE CLARIFY ON GAS RISER |
| | |
| | 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2017 FUEL GAS CODE SEC. 304. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2017 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, |
| | SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL |
| | GAS CODE SEC. 502 THRU 505. |
| | |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND |
| | INSTALLATION GUIDES FOR ALL GAS EQUIPMENTAND REGULATORS |
| | TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, |
| | AND FBC-2017 FUEL GAS SEC. 402.2 |
| | |
| | 8. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW |
| | CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO |
| | BE DOWN STREAM OF MANUAL VALVE. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |