Plan Review Notes
Plan Review Notes For Permit 19061408
Permit Number 19061408
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-08-08 13:31:18LETTER OF COMPLIANCE WITH NFPA PROVIDED AND ATTACHED TO
 THE RECORD. PML 8/16/19
  
  
 2 REVIEW COMMENTS:
  
  
  
 1) I CAN NOT READILY SEE NOR IDENTIFY WHERE OF HOW THE
 PREVIOUS FIRE COMMENTS WERE ADDERESSED.
  
 PLEASE ADDRESS EACH FIRE COMMENT WITH EITHER NUMBERED
 NARRATIVE AND/OR PLAN SHEET REVISION CLOUDS.
  
  
 *******************************************************
 *******************************************************
 *******
  
 THE COMMENTS BELOW ARE THE ORIGANL FIRE COMMENTS THAT
 HAVE NOT BEEN ADAQUATELY ADDRESSED.
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL SUBMITTED TO DETERMINE
 COMPLIANCE AND INTENT TO COMPLY WITH THE APPLICABLE
 REQUIRMENTS OF NFPA 72, 2013 ED.
  
 THE PROPOSED PROJECT INSTALLATION SHALL COMPLY WITH
 NFPA 72 AND OTHER APPLICABLE CODES.
  
 27.7.1 REQUIREMENTS FOR METALLIC AND FIBER-OPTIC
 SYSTEMS ?
 METALLIC AND FIBER-OPTIC INTERCONNECTIONS.
  
 27.7.1.1.1 EXTERIOR METALLIC, FIBER-OPTIC CABLE AND
 WIRE SHALL
 CONFORM TO INTERNATIONAL MUNICIPAL SIGNAL ASSOCIATION
 (IMSA) SPECIFICATIONS OR AN APPROVED EQUIVALENT.
 EXCEPTION: WHERE CIRCUIT CONDUCTORS OR FIBER-OPTIC
 STRANDS ARE PROVIDED BY
 A PUBLIC UTILITY ON A LEASE BASIS, IMSA SPECIFICATIONS
 SHALL NOT APPLY.
 27.7.1.1.2 WHERE A PUBLIC BOX IS INSTALLED INSIDE A
 BUILDING,
 THE CIRCUIT FROM THE POINT OF ENTRANCE TO THE PUBLIC
 BOX SHALL
 BE INSTALLED IN RIGID METAL CONDUIT, INTERMEDIATE METAL
 CONDUIT,
 OR ELECTRICAL METALLIC TUBING IN ACCORDANCE WITH NFPA
 70,
 NATIONAL ELECTRICAL CODE.
 EXCEPTION: THIS REQUIREMENT SHALL NOT APPLY TO WIRELESS
 BOX SYSTEMS.
 27.7.1.1.3 WIRES AND FIBER-OPTIC STRANDS SHALL BE
 TERMINATED
 SO AS TO PREVENT BREAKING FROM VIBRATION OR STRESS.
 27.7.1.1.4 CIRCUIT CONDUCTORS AND FIBER-OPTIC CABLES ON
 TERMINAL
 RACKS SHALL BE IDENTIFIED AND ISOLATED FROM CONDUCTORS
 OF
 OTHER SYSTEMS WHEREVER POSSIBLE AND SHALL BE PROTECTED
 FROM
 MECHANICAL INJURY.
 27.7.1.2 CABLES. THE REQUIREMENTS OF 27.7.1.2 SHALL
 APPLY TO
 27.7.1.3 THROUGH 27.7.1.6.
 27.7.1.2.1 EXTERIOR METALLIC AND FIBER-OPTIC CABLE AND
 WIRE SHALL
 CONFORM TO IMSA SPECIFICATIONS OR AN APPROVED
 EQUIVALENT.
 27.7.1.2.2 OVERHEAD, UNDERGROUND, OR DIRECT BURIAL
 CABLES
 SHALL BE SPECIFICALLY APPROVED FOR THE PURPOSE.
 27.7.1.2.3 METALLIC AND FIBER-OPTIC CABLES USED IN
 INTERIOR INSTALLATIONS
 SHALL COMPLY WITH NFPA 70, NATIONAL ELECTRICAL CODE,
 AND SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND PRACTICES.
 27.7.1.2.4 CONDUCTORS AND/OR FIBER-OPTIC STRANDS USED
 TO
 TRANSMIT SIGNALS OF OTHER SYSTEMS THAT ARE UNDER THE
 CONTROL OF
 A GOVERNMENTAL AGENCY SHALL BE PERMITTED TO BE
 CONTAINED
 WITHIN THE SAME MULTI-CONDUCTOR CABLE AS CONDUCTORS
 AND/OR
 FIBER-OPTIC STRANDS USED TO TRANSMIT SIGNALS OF PUBLIC
 EMERGENCY
 ALARM REPORTING SYSTEMS.
 27.7.1.2.5 BY SPECIAL PERMISSION AS DEFINED IN NFPA70,
 CABLES
 NOT UNDER THE CONTROL OF A GOVERNMENTAL AGENCY SHALL BE
 PERMITTED
 TO CONTAIN CONDUCTORS AND/OR FIBER-OPTIC STRANDS USED
 TO TRANSMIT SIGNALS OF A PUBLIC EMERGENCY ALARM
 REPORTING
 SYSTEM.
 27.7.1.2.6 SIGNALING WIRE AND FIBER-OPTIC CABLES
 CONTAINING
 METALLIC PROTECTION OR STRENGTH MEMBERS SHALL COMPLY
 WITH
 27.7.1.2.6.1 AND 27.7.1.2.6.2.
 27.7.1.2.6.1 SIGNALING WIRES SUPPLIED BY A POWER SOURCE
 HAVING
 A VOLTAGE AND/OR CURRENT RATING SUFFICIENT TO INTRODUCE
 A
 HAZARD SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70,
 NATIONAL
 ELECTRICAL CODE, ARTICLE 760, PART II
 27.7.1.2.6.2 FIBER-OPTIC CABLES CONTAINING METALLIC
 PROTECTION
 OR STRENGTH MEMBERS SHALL BE GROUNDED AND PROTECTED
 IN ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL CODE.
 27.7.1.2.7 ALL METALLIC CABLES, WITH ALL TAPS AND
 SPLICES MADE,
 SHALL BE TESTED FOR INSULATION RESISTANCE WHEN
 INSTALLED BUT BEFORE
 CONNECTION TO TERMINALS. SUCH TESTS SHALL INDICATE AN
 INSULATION
 RESISTANCE OF AT LEAST 200 MEGOHMS PER MILE BETWEEN
 ANY ONE CONDUCTOR AND ALL OTHER CONDUCTORS, THE SHEATH,
 AND
 THE GROUND.
  
 27.7.1.3 UNDERGROUND CABLES.
 27.7.1.3.1 UNDERGROUND METALLIC AND FIBER-OPTIC CABLES
 IN
 DUCT OR DIRECT BURIAL SHALL BE PERMITTED TO BE BROUGHT
 ABOVEGROUND ONLY AT LOCATIONS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
 27.7.1.3.1.1 PROTECTION FROM PHYSICAL DAMAGE OR HEAT
 INCIDENTAL
 TO FIRES IN ADJACENT BUILDINGS SHALL BE PROVIDED.
 27.7.1.3.2 ONLY FIBER-OPTIC AND POWER-LIMITED CABLES
 AND CONDUCTORS
 SHALL BE PERMITTED TO BE LOCATED IN DUCT SYSTEMS AND
 MANHOLES THAT CONTAIN POWER-LIMITED PUBLIC EMERGENCY
 ALARM
 REPORTING SYSTEM CONDUCTORS.
 27.7.1.3.3 WHERE LOCATED IN DUCT SYSTEMS OR MANHOLES
 THAT
 CONTAIN POWER CIRCUIT CONDUCTORS OVER 250 VOLTS TO
 GROUND,
 METALLIC AND FIBER-OPTIC EMERGENCY ALARM CABLES SHALL
 BE LOCATED
 AS FAR AS POSSIBLE FROM SUCH POWER CABLES AND SHALL BE
 SEPARATED FROM THEM BY A NONCOMBUSTIBLE BARRIER OR
 OTHER
 MEANS APPROVED BY THE AUTHORITY HAVING JURISDICTION TO
 PROTECT
 THE EMERGENCY ALARM CABLES FROM PHYSICAL DAMAGE.
 27.7.1.3.4 ALL CABLES INSTALLED IN MANHOLES SHALL BE
 RACKED
 AND MARKED FOR IDENTIFICATION.
 27.7.1.3.5 RACEWAYS OR DUCTS ENTERING BUILDINGS FROM
 UNDERGROUND
 DUCT SYSTEMS SHALL BE EFFECTIVELY SEALED WITH AN
 IDENTIFIED
 SEALING COMPOUND OR OTHER MEANS ACCEPTABLE TO THE
 AUTHORITY
 HAVING JURISDICTION TO PREVENT THE ENTRANCE OF MOISTURE
 OR GASES FROM THE UNDERGROUND DUCT SYSTEM.
 27.7.1.3.6 ALL CABLE JOINTS SHALL BE LOCATED IN
 MANHOLES, EMERGENCY
 RESPONSE FACILITIES, OR OTHER ACCESSIBLE LOCATIONS
 ACCEPTABLE
 TO THE AUTHORITY HAVING JURISDICTION WHERE EQUIVALENT
 PROTECTION
 IS PROVIDED TO MINIMIZE PHYSICAL DAMAGE TO THE CABLE.
 27.7.1.3.6.1 CABLE JOINTS SHALL BE MADE TO PROVIDE AND
 MAINTAIN
 CONDUCTIVITY, OPTICAL CONTINUITY FOR FIBER-OPTIC CABLE,
 INSULATION,
 AND PROTECTION AT LEAST EQUAL TO THAT AFFORDED BY THE
 CABLES THAT ARE JOINED.
 27.7.1.3.6.2 OPEN CABLE ENDS SHALL BE SEALED AGAINST
 MOISTURE.
 27.7.1.3.7 DIRECT-BURIAL CABLE, WITHOUT ENCLOSURE IN
 DUCTS,
 SHALL BE LAID IN GRASS PLOTS, UNDER SIDEWALKS, OR IN
 OTHER PLACES
 WHERE THE GROUND IS NOT LIKELY TO BE OPENED FOR OTHER
 UNDERGROUND
 CONSTRUCTION.
 27.7.1.3.7.1 WHERE SPLICES ARE MADE, SUCH SPLICES SHALL
 BE ACCESSIBLE
 FOR INSPECTION AND TESTS.
 27.7.1.3.7.2 SUCH CABLES SHALL BE BURIED AT LEAST 18
 IN.
 (500 MM) DEEP AND, WHERE CROSSING STREETS OR OTHER
 AREAS
 LIKELY TO BE OPENED FOR OTHER UNDERGROUND CONSTRUCTION,
 SHALL
 BE IN DUCT OR CONDUIT.
 27.7.1.6 WIRING INSIDE BUILDINGS.
 27.7.1.6.1 AT THE COMMUNICATIONS CENTER, ALL
 CONDUCTORS,
 CABLES, AND FIBER-OPTIC CABLES SHALL EXTEND AS DIRECTLY
 AS POSSIBLE
 TO THE OPERATIONS CENTER IN CONDUITS, DUCTS, SHAFTS,
 RACEWAYS,
 OR OVERHEAD RACKS AND TROUGHS LISTED OR IDENTIFIED AS
 SUITABLE
 TO PROVIDE PROTECTION AGAINST PHYSICAL DAMAGE.
 27.7.1.6.2* WHERE INSTALLED IN BUILDINGS, CONDUCTORS
 AND
 FIBER-OPTIC CABLES SHALL BE INSTALLED IN ANY OF THE
 FOLLOWING WIRING
 METHODS:
 (1) ELECTRICAL METALLIC TUBING
 (2) INTERMEDIATE METAL CONDUIT
 (3) RIGID METAL CONDUIT
 EXCEPTION: RIGID NONMETALLIC CONDUIT SHALL BE PERMITTED
 WHERE APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
 27.7.1.6.3 CONDUCTORS AND FIBER-OPTIC CABLES SHALL HAVE
 AN
 APPROVED INSULATION. THE INSULATION OR OTHER OUTER
 COVERING
 SHALL BE FLAME-RETARDANT AND MOISTURE RESISTANT.
 27.7.1.6.4 CONDUCTORS AND FIBER-OPTIC CABLES SHALL BE
 INSTALLED
 AS FAR AS POSSIBLE WITHOUT SPLICES OR JOINTS. SPLICES
 OR
 JOINTS SHALL BE PERMITTED ONLY IN LISTED JUNCTION OR
 TERMINAL
 BOXES.
 27.7.1.6.4.1 ENCLOSURES CONTAINING PUBLIC EMERGENCY
 ALARM
 REPORTING SYSTEM CIRCUITS SHALL BE PROVIDED WITH RED
 COVERS OR
 DOORS. THE WORDS ?PUBLIC EMERGENCY ALARM REPORTING
 SYSTEM
 CIRCUIT? SHALL BE CLEARLY MARKED ON ALL TERMINAL AND
 JUNCTION
 LOCATIONS TO PREVENT UNINTENTIONAL INTERFERENCE.
 27.7.1.6.4.2 WIRE AND FIBER-OPTIC TERMINALS, TERMINAL
 BOXES,
 SPLICES, AND JOINTS SHALL CONFORM TO NFPA 70, NATIONAL
 ELECTRICAL
 CODE.
 27.7.1.6.5 METALLIC AND FIBER-OPTIC CABLES AND WIRING
 EXPOSED
 TO A HAZARD SHALL BE PROTECTED IN AN APPROVED MANNER.
 27.7.1.6.6 METALLIC AND FIBER-OPTIC CABLE TERMINALS AND
 CROSS-CONNECTING FACILITIES SHALL BE LOCATED IN OR
 ADJACENT TO
 THE OPERATIONS ROOM.
 27.7.1.6.7 WHERE SIGNAL CONDUCTORS, NON-DIELECTRIC
 FIBER-OPTIC
 CABLES, AND ELECTRIC LIGHT AND POWER WIRES ARE RUN IN
 THE SAME
 SHAFT, THEY SHALL BE SEPARATED BY AT LEAST 2 IN. (51
 MM), OR EITHER
 SYSTEM SHALL BE ENCASED IN A NONCOMBUSTIBLE ENCLOSURE.
  
 PLEASE REVIEW AND PROVIDE SPECIDIC DETAILS AND/OR
 PROVIDE AN EOR REVIEW OF COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL