| Plan Review Notes For Permit 19061383 |
| Permit Number |
19061383 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-01 15:11:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | | | | 1) IT IS UNCLEAR WHAT AND WHERE THE SCOPE IS. | | | | | | PLEASE CLEARLY IDENTIFY WHICH HEADS ARE AFFECTED BY | | | CLOUDING AND/OR OTHER CLEAR INDICATORS. | | | | | | | | | | | | 2) HOW MANY SPRINKLERS ARE AFFECTED ON EACH LEVE? | | | | | | PLEASE SO A LEGEND WITH EXACT COUNTS AND SPRINKLER | | | INDENTIFICATION. | | | | | | | | | | | | 3) THERE ARE SOME STAIRWAY AREAS INDICATED; HOWEVER, | | | SPRINKLER PROTECTION IN THESE AREAS DO NOT APPEAR TO BE | | | SPACED CORRECTLY, IT AT ALL, | | | | | | PLEASE REVIEW THESE AREAS AND ENSURE CODE COMPLIANT | | | COVERAGE. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|