2019-07-01 15:11:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) IT IS UNCLEAR WHAT AND WHERE THE SCOPE IS.
  
 PLEASE CLEARLY IDENTIFY WHICH HEADS ARE AFFECTED BY
 CLOUDING AND/OR OTHER CLEAR INDICATORS.
  
  
  
 2) HOW MANY SPRINKLERS ARE AFFECTED ON EACH LEVE?
  
 PLEASE SO A LEGEND WITH EXACT COUNTS AND SPRINKLER
 INDENTIFICATION.
  
  
  
 3) THERE ARE SOME STAIRWAY AREAS INDICATED; HOWEVER,
 SPRINKLER PROTECTION IN THESE AREAS DO NOT APPEAR TO BE
 SPACED CORRECTLY, IT AT ALL,
  
 PLEASE REVIEW THESE AREAS AND ENSURE CODE COMPLIANT
 COVERAGE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  