2019-07-16 12:54:58FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: COLUMN HEADING
 ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT
 APPROVAL?; USED THE INSTALLATION LEGEND ON PAGE 11 OF
 THE SUBMITTED PRODUCT APPROVALS AND PROVIDE THE
 ALPHABETICAL LETTER THAT CORRESPONDS WITH THE
 INSTALLATION METHODS PROVIDED ON PAGES 6 & 7 FOR THE
 TOP AND BOTTOM INSTALLATIONS. EXAMPLE: ? HV WALL HEADER
 INSTALLATION IS THE ONLY ALLOWABLE WALL HEADER
 INSTALLATION FOR CBS SUBSTRATES. INSTALLATION METHODS
 D, E, AND F IS ALLOWABLE FOR WALL SILL INSTALLATIONS
 FOR CBS SUBSTRATES. PLEASE VERIFY ANCHOR SPACINGS;
 EXAMPLE (M) KEYSTONE MOUNTING INSTALLATION REQUIRES
 ANCHORS 4? O.C. FOR SPANS LARGER THAN 6?-0? UP TO 8?-0?
 MAX.