| Plan Review Notes For Permit 19061302 |
| Permit Number |
19061302 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-01-14 14:28:01 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A SITE PLAN. IDENTIFY WHICH STRUCTURE THIS | | | PERMIT IS FOR. | | | | | | 2. LOCATE OPENINGS FOR WINDOW REPLACEMENT. PROVIDE | | | ROUGH OPENING SIZES AND DESIGN PRESSURES OF EACH | | | OPENING. | | | | | | 3. PROVIDE DETAIL FOR EXTERIOR WALL IN-FILL. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | |
|