| 2019-07-08 08:39:16 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY C. THE |
| | COMPONENT AND CLADDING PRESSURES AND THE EXPOSURE |
| | CATEGORY LISTED ON THE FORM THAT WAS SUBMITTED IS |
| | EXPOSURE CATEGORY B. IN ORDER TO USE EXPOSURE B, YOU |
| | WILL NEED TO PROVIDE A SITE SPECIFIC ANALYSIS SHOWING |
| | THAT THIS PROPERTY IS ACTUALLY EXPOSURE CATEGORY B. THE |
| | ANALYSIS IS REQUIRED TO BE PRODUCED BY AND SIGNED AND |
| | SEALED BY A FLORIDA LICENSED PROFESSIONAL ENGINEER. FBC |
| | 107.2.1 & FS 471 |
| | |
| | 2) THE MEAN ROOF HEIGHT FOR THIS BUILDING IS 25 FEET |
| | PER THE INFORMATION THAT YOU PROVIDED. YOU NEED TO USE |
| | THE MEAN ROOF HEIGHT OF THE BUILDING FOR DETERMINING |
| | THE COMPONENT AND CLADDING PRESSURES FOR THE SHUTTERS. |
| | FBC R301.2.1 |
| | |
| | FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN INSTALLATION |
| | SCHEDULE AND KEY PLAN FOR THE STORM PANELS. SPECIFY THE |
| | OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR, |
| | ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL |
| | SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE |
| | APPLICABLE SECTION NUMBER FROM THE INSTALLATION |
| | DRAWINGS. I HAVE INCLUDED A LINK TO THE CONSTRUCTION |
| | SERVICES DEPARTMENT SITE THAT HAS MANY OF THE RELATED |
| | FORMS INCLUDING |
| | THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| | DEVICES. |
| | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ |
| | |
| | |