| Plan Review Notes For Permit 19061262 |
| Permit Number |
19061262 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-03 16:15:26 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | PLAN REVIEW DENIED: | | | | | | FBC B 107. PROVIDE THE TEST REPORTS TO VERIFY RESULTS | | | PERTHE FOLLOWING CODE SECTIONS: | | | | | | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE | | | AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT | | | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 | | | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 492. |
|