Plan Review Notes
Plan Review Notes For Permit 19061189
Permit Number 19061189
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-29 18:25:45***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
 2ND BUILDING REVIEW DENIED. PLEASE REVIEW AND RESUBMIT
 PERMIT APPLICATION. PLEASE BE SURE THAT ALL NEW
 DOCUMENTS BY DESIGNER OF RECORD HAVE AN ORIGINAL
 SIGNATURE AND SEAL.
  
  
 1) FBC B 107.2.1 PROVIDE NOTE ON PLANS CLARIFYING THE
 SCOPE OF WORK AND INCLUDE THE NOTE THAT NO EXTERIOR
 AND/OR STRUCTURAL WALL OR ROOF MEMBERS WERE DAMAGED.
  
 2) FBC 107.2.1. PAGE 33 OF 77 LIVING ROOM APPEARS TO
 SHOW A NEW (VINYL) SLIDING GLASS DOOR REPLACEMENT. THE
 N.O.A SUBMITTED IS FOR ALUMINUM SLIDING GLASS DOORS NOT
 VINYL. PLEASE CLARIFY WHICH DOOR IS TO BE USED AND
 PROVIDE THE REQUIRED N.O.A.
  
 3) SHEET 41 OF 77 ITEM 242 REPLACEMENT OF VINYL WINDOW?
 JALOUSIE. MISSING PRODUCT APPROVALS.
 2017 FBC?B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20?3.005,
 RULE 9N?3 NOV. 01/ 2010 (31) SUB?CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (THE WINDOW PRODUCT APPROVAL THAT WAS SUBMITTED IS FOR
 ALUMINUM WINDOWS NOT VINYL).
  
 4) SHEET 46 OF 77 EXTERIOR DOOR ENTRY/ FOYER ITEM 307
 EXTERIOR DOOR METAL INSULATED, 319 & 331. MISSING
 PRODUCT APPROVAL.
 2017 FBC?B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20?3.005,
 RULE 9N?3 NOV. 01/ 2010 (31) SUB?CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (NO PRODUCT APPROVALS WERE SUBMITTED FOR THESE DOORS).
  
 5) NEITHER THE PLAN NOR 77 SHEETS OF SCOPE OF WORK
 PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW PRODUCT
 APPROVALS. 2017 FBC?B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE?RESISTING SYSTEM OF THE
 STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3?SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  