| Plan Review Notes For Permit 19061189 |
| Permit Number |
19061189 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-11 15:42:49 | PLUMBING COMMEMTS: APPROVED | | | PLUMBING PROVISO | | | 1. SCOPE IS LIMITED TO THE FOLLOWING: | | | A. REMOVE EXISTING BATHROOM FIXTURES AND KITCHEN SINK | | | TO FACILITATE THE WORK. | | | B. REMOVING DAMAGED PORTIONS OF PIPING SYSTEMS, | | | REPLACING WITH NEW AND TESTING. AN INSPECTION OF THE | | | WET WALLS IS REQUIRED PRIOR TO COVERIUNG OF ANY WORK. | | | C. ANTI-SCALD TUB SHOWER VALVE SHALL BE INSTALLED FOR | | | THE BATHTUB PER FBC PL 4254.3 | | | D. RESET EXISTING FIXTURES IN ORIGINAL LOCATIONS. | | | 2. IF ANY FLOOR PENETRATIONS ARE OPENED TO FACILITATE | | | THE WORK PROCESS, THEN A UL LISTED ASSEMBLY SHALL BE | | | SUBMITTED AND APPROVED. SAID PENETRATION SHALL BE | | | INSPECTED FOR COMPLIANCE WITH THE UL RATED ASSEMBLY. | | | 3. ALL PLUMBING WORK PER STATE AND CITY CODES SUBJECT | | | TO FIELD INSPECTOR'S APPROVAL | | | 4. IN ACCORDANCE WITH FBC PL 604.9, ONLY WATER HAMMER | | | ARRESTORS CONFORMING TO ASSE 1010 SHALL BE INSTALLED. | | | CAPPED AIR CHAMBERS ARE PROHIBITED. | | | |
|