| Notes |
| Date |
Text |
| 2019-06-25 08:15:37 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- FLAT ROOF NOA 15-1201.09 SUBMITTED: SELECTED | | | ASSEMBLY ON PAGE 41 OF 49 DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED | | | AND SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED | | | BY LIMITATION #7 ON LAST PAGE OF NOA. NEED THE | | | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | NOTE: TAKE INTO CONSIDERATION THAT BUILDING IS LOCATED | | | IN EXPOSURE D. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|