| 2019-07-24 15:29:14 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19061141 |
| | 2ND REVIEW: JULY 24, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 301.2(2) TABLE FBC[R] |
| | PLEASE PROVIDE WIND DESIGN DATA FOR NEW WINDOWS. |
| | PROJECT DATA: |
| | TYPE OF WALL CONSTRUCTION = _________(WOOD, MASONRY?) |
| | RISK CATEGORY = ___(II) |
| | EXPOSURE CATEGORY = ___(B,C OR D) |
| | BUILDING CLASSIFICATION = __________(ENCLOSED) |
| | MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO ROOF DECK) |
| | WIND SPEED V ULT = _____(170) |
| | WIND SPEED V ASD = _____(132) |
| | COMPONANT & CLADDING: |
| | FBC TABLE 301.2(2) FBC[R] |
| | DESIGN PRESSURE = +___ & -___ |
| | 301.2(3) FBC[R] CHECK EXPOSURE AND M.R.H. TO DETERMINE |
| | IF ADJUSTMENT FACTOR NEEDED. |
| | MULTIPLE DESIGN PRESUURES BY THE ADJUSTMENT FACTOR IF < |
| | OR > 1.00 |
| | |
| | PROVIDE PRESSURE ON EACH WINDOW/DOOR AND INDICATE IF |
| | THE OPENING IS IN THE INTERIOR OR EXTERIOR ZONE. |
| | |
| | 1A) 2ND REVIEW ADDITIONAL COMMENT: |
| | THE DRAWING SHEET PROVIDED IS THE SAME SHEET PROVIDED |
| | WITH THE INITIAL PERMIT. |
| | IT STATES THAT WINDOWS ARE EXISTING AND DOES NOT SHOW |
| | THE NEW WORK. |
| | PLEASE PROVIDE A SHEET TO SHOW NEW WORK, WINDOW |
| | SCHEDULE AND PREVIOUSLY REQUESTED DESIGN DATA. |
| | I REVIEWED INITIAL PERMIT SHEETS AND THIS DESIGN DATA |
| | WAS NOT ALREADY PROVIDED SINCE ORIGINALLY THERE WAS NO |
| | WINDOW/DOOR REPLACEMENT. |
| | |
| | 2) OK - PRODUCT APPROVALS SUBMITTED AND STAMPED FOR |
| | APPROVAL. |
| | |
| | NOTES: |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |