| Plan Review Notes For Permit 19061126 |
| Permit Number |
19061126 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-19 11:12:08 | PLAN DENIED | | | PROVIDE EQUIPMENT SCHEDULE ON PLAN. | | | PROVIDE LOCATION OF CONDENSER ON PLAN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|