Plan Review Notes
Plan Review Notes For Permit 19061126
Permit Number 19061126
Review Stop E
Sequence Number 1
Notes
Date Text
2019-07-18 16:41:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SMOKE ALARMS MISSING R314 FBC
  
 OUTLET ON THE OUTDOOR SIDE MISSING
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
 CODE IS BASED ON 2014 NEC NOT 2008