| 2019-07-12 10:51:01 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19061126 |
| | REVIEWED: JULY 12, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS: |
| | - PLEASE SHOW LOCATION OF SMOKE DETECTORS FOR NEW |
| | ADDITION. |
| | |
| | 2) 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED |
| | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA |
| | STATUTES. |
| | - PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS. |
| | |
| | 3) 103.1.1.2 FBC[RE] THE ENERGY CALCULATIONS STATE |
| | CAHTHEDRAL CEILING. |
| | - IF CATHEDRAL CEILING WAS BEING USED THE AREA WOULD BE |
| | MORE. PLEASE ADJUST ENERGY CALCULATIONS TO STATE THE |
| | TYPE OF CEILING BEING UTILIZED. ALSO, CHECK ROOF TYPE |
| | SAYS COMPOSITION SHINGLES. |
| | |
| | 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS, WINDOW MULL (IF APPLICABLE), DOORS AND |
| | TRANSOMS, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED. |
| | - ALSO, CHECK WINDOW SCHEDULE ON SHEET 9. SIZES DON?T |
| | MATCH WHAT IS SHOWN ON FLOOR PLAN, AND I DON?T SEE |
| | WINDOW IN BATHROOM ON THE SCHEDULE. |
| | |
| | 5) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED. |
| | |
| | NOTE: |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |