2019-11-19 18:54:243RD REVIEW 19061087
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED PREVIOUS COMMENTS NOT
 COMPLIED WITH FROM 1ST REVIEW.
  
 1.DRINKING FOUNTAIN SHALL COMPLY WITH FBC PL 410.3 AND
 FBC ACC SECTIONS 602 AND 306. PER WPB 107.2.1, PROVIDE
 DETAIL SHOWING COMPLIANCE. SOME OF THIS INFORMATION HAS
 BEEN PREVIOUSLY REQUESTED AND HAS NOT BEEN RESPONDED
 TO. THE WATER FOUNTAIN HAS BEEN ADDED TO THE SCOPE OF
 THE PROJECTED PLEASE ADD THE FOLLOWING DETAIL TO SHOW
 COMPLIANCE WITH FBC ACC 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.2 CLEAR FLOOR SPACE. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 5.SECOND REQUEST: FBC ACC 604.5.2 -THE REAR WALL GRAB
 BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE. THE 36" BAR
 IS SHOWN WITH 6" FROM END OF THE BAR TO THE WALL THIS
 DOES NOT SHOW COMPLIANCE WITH FBC ACC 604.5.2 -THE REAR
 WALL GRAB BAR SHALL EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 PREVIOUS COMMENTS NOT COMPLIED WITH FROM 2ND REVIEW.
 1. THE TOILET PAPER DISPENSER IS SHOWN AT 36" OFF THE
 BACK WALL THIS DOES NOT COMPLY WITH FBC ACC 604.7,
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 6.PER FBC PL 607.1, HOT WATER IS REQUIRED TO THE
 SERVICE SINK.IT HAS NOT BEEN SHOWN ON WATER ISOMETRIC.
 IF YOUR USING A TANKLESS WATER HEATER WITH AN INTEGRAL
 TEMPERATURE LIMITING DEVISE FOR TEMPERED WATER TO THE
 LAVATORIES YOU CAN NOT USE THE SAME TANKLESS HEATER FOR
 THE HOT WATER REQUIRED AT THE SERVICE SINK THE
 TEMPERATURE FOR HOT WATER IS HIGH THAN THAT OF TEMPERED
 WATER. IN ORDER FOR THIS TO BE CODE COMPLIANT IT WILL
 BE REQUIRED THAT YOU USE TWO DIFFERENT WATER HEATERS OR
 A SINGLE WATER HEATER WITH AN OUTLET TEMPERATURE OF
 OVER 110 DEG. AND TEMPERING EACH LAVATORY TO A
 TEMPERATURE BELOW 110DEG AND SUPPLING HOT WATER OVER
 110 DEG. TO THE SERVICE SINK. PER FBC PL 607.1 AND
 416.5
  
 7.WATER DISTRIBUTION FLOOR PLAN AND RISER DIAGRAM DO
 NOT MATCH. PER WPB FBC 107.2.1, CLARIFY. THE FLOOR PLAN
 SHOWS SEPARATE BRANCHES FOR THE COLD WATER FOR THE
 WATER FOUNTAIN, LAVATORY SINK AND SERVICE SINK THE
 ISOMETRIC SHOWS A SINGLE BRANCH OFF THE MAIN TO ALL
 FIXTURES.
  
 8. THE SANITARY ISOMETRIC DRAWING DOES NOT MATCH THE
 FLOOR PLAN THE SANITARY ISOMETRIC SHOWS A SINGLE BRANCH
 OFF THE MAIN BUILDING DRAIN THE FLOOR PLAN SHOWS
 SEPARATE BRANCHES FOR EACH FIXTURE AND BATHROOM
 GROUP.PER WPB FBC 107.2.1, CLARIFY
  
 9.PER FBC PL (E)607.5, PROVIDE INSULATION FOR THE HOT
 WATER. PROVIDE SPECIFICATION PER WPB FBC 107.2.1.
  
  
 NEW COMMENTS:
  
 1. ON THE WATER ISOMETRIC DRAWING THERE IS THE
 FOLLOWING VIOLATIONS.
 A) THE HOT IS SHOWN ON THE RIGHT SIDE OF THE LAVATORY'S
 AND COLD ON THE LEFT IT NEEDS TO BE REVERSED.PER FBC PL
 607.4
 B) THE SUPPLY TO THE WC IS SHOWN AS HOT IT SHALL BE
 SHOWN AS COLD AND A SEPARATE BRANCH FOR TEMPERED WATER
 TO THE LAVATORY. PER WPB AMEND TO FBC 107.2.1
 C) THE HOT SUPPLY FOR THE SERVICE SINK IS MISSING. PER
 FBC PL 607.1
 D) THE SIZE OF THE OF THE MAIN FEED TO THIS UNIT AT
 1/2" APPEARS TO BE UNDERSIZED THE MINIMUM WATER SERVICE
 IS 3/4" THOUGH THIS IS NOT A SEPARATE STRUCTURE THE
 SAME PRINCIPAL APPLIES. APPENDIX E IN THE PLUMBING CODE
 IS NOT ENFORCEABLE BUT IS A GOOD SIZING METHOD, PLEASE
 PROVIDE THE SIZING CALCULATION THAT WERE USED TO
 DETERMINE PIPE SIZING ON THIS PROJECT. PER AMEND TO FBC
 107.2.1
 E) A VALVE IS REQUIRED ON THE COLD WATER DROP FROM MAIN
 LINE AND AT THE WATER HEATER AND EACH FIXTURE. PER FBC
 PL 606.1(5)(8), 606.2(1)
  
 2. SHOW COMPLIANCE OR PROVIDE NOT ON PLAN. 606.3 ACCESS
 TO VALVES. ACCESS SHALL BE PROVIDED TO ALL FULL-OPEN
 VALVES AND SHUTOFF VALVES.
  
 3.PROVIDE SPECIFICATIONS AND INSTILLATION GUIDE FOR
 TANKLESS HEATER. MANUFACTURE SPECIFICATION SHALL SHOW
 SIZE OF WATER HEATER IS APPROVED FOR THE DEMAND OF ALL
 PLUMBING FIXTURE. PER WPB FBC 107.2.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  