2019-11-15 17:00:242ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19061087
 11/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE COMMENTS FROM THE 1ST AND 2ND REVIEW PRINTED BELOW
 ARE STILL COMPLETELY ADDRESSED.
  
 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE
 OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS
 CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE
 NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE
 INDICATING- SEE TABLE 403.3.1.1 FBC M.
 THE LARGE OPEN SPACE IS LISTED AS A LOBBY HOWEVER THE
 ARCHITECTURAL PLANS APPEAR TO INDICATE A MULTI-PURPOSE
 ROOM OR RECEPTION AREA. RECEPTION AREAS ARE CALCULATED
 AT 30 PERSONS PER 1000 SQ. FT. + 0.06 CFMS PER SQ. FT.
 PLEASE CORRECT THE CALCULATIONS.
  
 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE
 LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE
 AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION
 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE
 SUPPLY SYSTEMS.
 DUCT SMOKE DETECTORS ARE REQUIRED IN THE "SUPPLY
 SYSTEMS" OF EACH AIR HANDLER. THE CORRECTED PLAN IS
 SHOWING THEM IN THE "RETURN PLENUMS" OF THE AIR
 HANDLERS. ALSO THERE ARE NOTES INDICATING THEY ARE TO
 BE LOCATED IN THE AC COMPRESSORS, WHICH IS NOT A
 REQUIRED LOCATION. PLEASE CONSULT WITH THE MANUFACTURER
 BECAUSE THE INSTALLATION MAY NOT COMPLY WITH
 INSTALLATION GUIDELINES AND MAY VOID THE WARRANTIES.
  
 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE
 PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS
 DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE
 EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING
 LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE
 OVERSIZED- SEE SECTION C403.2.2 FBC EC.
 AS NOTED ABOVE NO INTERNAL LOADS HAVE BEEN CALCULATED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  