| Date |
Text |
| 2019-11-15 17:00:24 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19061087 |
| | 11/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE COMMENTS FROM THE 1ST AND 2ND REVIEW PRINTED BELOW |
| | ARE STILL COMPLETELY ADDRESSED. |
| | |
| | 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE |
| | OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS |
| | CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE |
| | NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE |
| | INDICATING- SEE TABLE 403.3.1.1 FBC M. |
| | THE LARGE OPEN SPACE IS LISTED AS A LOBBY HOWEVER THE |
| | ARCHITECTURAL PLANS APPEAR TO INDICATE A MULTI-PURPOSE |
| | ROOM OR RECEPTION AREA. RECEPTION AREAS ARE CALCULATED |
| | AT 30 PERSONS PER 1000 SQ. FT. + 0.06 CFMS PER SQ. FT. |
| | PLEASE CORRECT THE CALCULATIONS. |
| | |
| | 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE |
| | LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE |
| | AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION |
| | 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE |
| | SUPPLY SYSTEMS. |
| | DUCT SMOKE DETECTORS ARE REQUIRED IN THE "SUPPLY |
| | SYSTEMS" OF EACH AIR HANDLER. THE CORRECTED PLAN IS |
| | SHOWING THEM IN THE "RETURN PLENUMS" OF THE AIR |
| | HANDLERS. ALSO THERE ARE NOTES INDICATING THEY ARE TO |
| | BE LOCATED IN THE AC COMPRESSORS, WHICH IS NOT A |
| | REQUIRED LOCATION. PLEASE CONSULT WITH THE MANUFACTURER |
| | BECAUSE THE INSTALLATION MAY NOT COMPLY WITH |
| | INSTALLATION GUIDELINES AND MAY VOID THE WARRANTIES. |
| | |
| | 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE |
| | PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS |
| | DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE |
| | EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING |
| | LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE |
| | OVERSIZED- SEE SECTION C403.2.2 FBC EC. |
| | AS NOTED ABOVE NO INTERNAL LOADS HAVE BEEN CALCULATED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | BUILDING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |