2019-11-16 08:26:152017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061087
 ADD: 950 EVERNIA ST. 1ST FLOOR.
 CONT: NKT CONSTRUCTION SERVICES.
 TEL: 561-662-8150
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. NOV. 16TH/2019
 ACTION: DENIED
  
 1-7 COMPLIED.
  
 8) SEMI-COMPLIED.
 8A) THIS REVIEW THE DESIGNER OF RECORD HAS SHOWN THE
 LOCATION OF A HI-LOW DRINKING FOUNTAIN. SINCE THE
 DRINKING FOUNTAIN IS NOT LOCATED IN AN ALCOVE THE
 DRINKING FOUNTAIN WILL ALSO NEED TO SHOW COMPLIANCE
 WITH PROTRUDING OBJECTS. PLEASE REVIEW THE 2017
 FBC-ACCESSIBILITY CODE SECTION:
  
 307.2 PROTRUSION LIMITS. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80
 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL
 PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 8B) RESTROOMS, SEMI-COMPLIED. THE LIFE-SAFETY SHEET NOW
 SHOWS ELEVATIONS FOR THE RESTROOMS. ONE ISSUE WITH THE
 ELEVATION VIEW IS THE DIMENSIONING FOR HEIGHTS OF THE
 WATER CLOSET GRAB BARS. I T APPEARS THAT THE
 MEASUREMENT IS BEING TAKEN FROM FINISH FLOOR TO THE
 CENTERLINE OF THE GRAB BAR. NOTE THE RANGE IS CORRECT
 BUT THE 2017 FBC-ACCESSIBILITY CODE DOES NOT TAKE THE
 MEASUREMENT TO THE CENTERLINE BUT FROM FINISH FLOOR TO
 THE TOP OF THE GRASPABLE SURFACE. THAT COULD MAKE AN
 ELEVATION CHANGE FROM 5/8 INCH TO 1 INCH HIGHER THAN
 WOULD BE ALLOWED IF THE CONTRACTOR PLACED THE GRAB BAR
 AT 36 INCHES FROM FINISH FLOOR TO CENTERLINE.
 2017 ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 8C) THE OTHER ISSUE IS WITH THE DIMENSIONING OF THE
 TOILET PAPER DISPENSER. THE ELEVATION DRAWINGS SHOW
 DIMENSIONING OF 36 INCHES FROM THE REAR WALL TO THE
 CENTERLINE OF THE DISPENSER. WITH NOT GIVING THE
 DIMENSION OF THE FRONT OF THE WATERCLOSET FROM OF THE
 BACK WALL THIS IS THEN AN UNKNOWN DISTANCE BETWEEN THE
 FRONT OF THE WATERCLOSET AND THE CENTERLINE OF THE
 DISPENSER. THE 2017 FBC-ACCESSIBILITY CODE REQUIRES
 DIMENSIONING FROM THE FRONT OF THE WATERCLOSET TO
 CENTERLINE OF THE DISPENSER.
  
 TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE 604.7
 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 9) NEW COMMENT. PLEASE REFER TO THE M-1 SHEET. THIS
 ISSUE IS WITH THE LOCATION OF SMOKE DETECTORS.
 THE PLANS LIST THE REQUIREMENT FOR SMOKE DETECTORS IN 2
 LOCATIONS, (1) SMOKE DETECTORS IN PLENUMS AND (2) SMOKE
 DETECTORS ARE TO BE IN COMPRESSORS.
 PLEASE UPDATE THE PLANS TO SHOW COMPLIANCE WITH:
  
 SMOKE DETECTOR LOCATIONS: 2017 FBC-B 907.3 FIRE SAFETY
 FUNCTIONS.
 907.3.1 DUCT SMOKE DETECTORS. SMOKE DETECTORS INSTALLED
 IN DUCTS SHALL BE LISTED FOR THE AIR VELOCITY,
 TEMPERATURE AND HUMIDITY PRESENT IN THE DUCT AND SHALL
 PERFORM THE INTENDED FIRE SAFETY FUNCTION IN ACCORDANCE
 WITH THIS CODE AND THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 2017 FBC-MECHANICAL CODE SECTION 606.2.1. TO PREVENT
 THE RECIRCULATION OF DANGEROUS QUANTITIES OF SMOKE, A
 DETECTOR APPROVED FOR AIR DUCT USE SHALL BE INSTALLED
 ON THE SUPPLY SIDE OF AIR-HANDLING SYSTEMS AS REQUIRED
 BY NFPA 90A. STANDARD FOR THE INSTALLATION OF AIR
 CONDITIONING AND VENTILATING SYSTEMS. SMOKE DETECTORS
 LISTED FOR USE IN AIR DISTRIBUTION SYSTEMS SHALL BE
 LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE
 CAPACITY GREATER THAN 2000 CUFT/MIN.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER