Plan Review Notes
Plan Review Notes For Permit 19061087
Permit Number 19061087
Review Stop P
Sequence Number 2
Notes
Date Text
2019-10-03 14:24:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1.DRINKING FOUNTAIN SHALL COMPLY WITH FBC PL 410.3 AND
 FBC ACC SECTIONS 602 AND 306. PER WPB 107.2.1, PROVIDE
 DETAIL SHOWING COMPLIANCE. SOME OF THIS INFORMATION HAS
 BEEN PREVIOUSLY REQUESTED AND HAS NOT BEEN RESPONDED
 TO.
 2.SECOND REQUEST: FBC ACC 604.2 -THE WATER CLOSET SHALL
 BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND
 TO ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL
 BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION. PER WPB FBC 107.2.1. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE.
 3.SECOND REQUEST: FBC ACC 604.4 -THE SEAT HEIGHT OF A
 WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES
 MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE TOP OF
 THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A
 LIFTED POSITION. PER WPB FBC 107.2.1. PER WPB 107.2.1,
 PROVIDE DETAIL SHOWING COMPLIANCE.
 4.SECOND REQUEST: FBC ACC 604.5.1 -THE SIDE WALL GRAB
 BAR SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL. PER WPB 107.2.1, PROVIDE
 DETAIL SHOWING COMPLIANCE.
 5.SECOND REQUEST: FBC ACC 604.5.2 -THE REAR WALL GRAB
 BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE.
 6.SECOND REQUEST: FBC ACC 609.4 -GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER WPB 107.2.1,
 PROVIDE DETAIL SHOWING COMPLIANCE.
 7.SECOND REQUEST: 606.2 -A CLEAR FLOOR SPACE FOR THE
 LAVATORIES COMPLYING WITH 305, POSITIONED FOR A FORWARD
 APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED. PER WPB FBC 107.2.1, REVISE DRAWING
 TO SHOW COMPLIANCE.
 8.SECOND REQUEST: 606.3 -LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER WPB 107.2.1, PROVIDE DETAIL
 SHOWING COMPLIANCE. ADDITIONALLY SHOW COMPLIANCE WITH
 FBC ACC SECTION 306.
 9.SECOND REQUEST: 603.3 -MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER WPB
 107.2.1, PROVIDE DETAIL SHOWING COMPLIANCE.
  
 ADDITIONAL COMMENTS:
 1.PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES (380 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM
 ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND
 GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE THAT
 CONTROLS DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS
 PAPER FLOW. PER WPB 107.2.1, PROVIDE DETAIL SHOWING
 COMPLIANCE.
 2.PER FBC ACC 604.6, FLUSH CONTROLS SHALL BE HAND
 OPERATED OR AUTOMATIC. HAND OPERATED FLUSH CONTROLS
 SHALL COMPLY WITH 309. FLUSH CONTROLS SHALL BE LOCATED
 ON THE OPEN SIDE OF THE WATER CLOSET EXCEPT IN
 AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH
 604.8.2. PER WPB 107.2.1, PROVIDE DETAIL SHOWING
 COMPLIANCE.
 3.PER FBC ACC 604.8.1.1, TOILET COMPARTMENT DOORS,
 INCLUDING DOOR HARDWARE, SHALL COMPLY WITH 404 EXCEPT
 THAT IF THE APPROACH IS TO THE LATCH SIDE OF THE
 COMPARTMENT DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF
 THE COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. DOORS SHALL BE LOCATED IN THE FRONT
 PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST
 FROM THE WATER CLOSET. WHERE LOCATED IN THE FRONT
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE SIDE WALL OR PARTITION FARTHEST FROM
 THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL OR
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE FRONT PARTITION. THE DOOR SHALL BE
 SELF-CLOSING. A DOOR PULL COMPLYING WITH 404.2.7 SHALL
 BE PLACED ON BOTH SIDES OF THE DOOR NEAR THE LATCH.
 TOILET COMPARTMENT DOORS SHALL NOT SWING INTO THE
 MINIMUM REQUIRED COMPARTMENT AREA. SEE ALSO FBC ACC
 604.8.1.7 AND ADVISORY 604.8.1.6 AND 604.8.1.7. PER WPB
 FBC 107.2.1, REVISE DRAWING TO SHOW COMPLIANCE.
 4.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 SCHEDULE WITH FIXTURE SPEC AND WATER USAGE
 REQUIREMENTS.
 5.PER WPB FBC 107.2.1, PROVIDE A WATER HEATER EQUIPMENT
 SCHEDULE SPECIFYING UNIT(S), GPM AND ELECTRICAL
 CHARACTERISTICS.
 6.PER FBC PL 607.1, HOT WATER IS REQUIRED TO THE
 SERVICE SINK.
 7.WATER DISTRIBUTION FLOOR PLAN AND RISER DIAGRAM DO
 NOT MATCH. PER WPB FBC 107.2.1, CLARIFY.
 8.SANITARY PIPING FLOOR PLAN AND RISER DIAGRAM DO NOT
 MATCH. PER WPB FBC 107.2.1, CLARIFY.
 9.PER FBC PL (E)607.5, PROVIDE INSULATION FOR THE HOT
 WATER. PROVIDE SPECIFICATION PER WPB FBC 107.2.1.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19061087 950 EVERNIA ST
  
  