Plan Review Notes
Plan Review Notes For Permit 19061087
Permit Number 19061087
Review Stop M
Sequence Number 2
Notes
Date Text
2019-10-03 08:44:512ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19061087
 10/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: 2ND REQUEST TO IDENTIFY AND LABEL THE LARGE
 OPEN ROOMS AND PROVIDE VENTILATION CALCULATIONS
 CONSISTENT WITH THE USE OF THESE SPACES. THE SPACES ARE
 NOT OFFICES AS THE CALCULATIONS ON THE PLAN ARE
 INDICATING- SEE TABLE 403.3.1.1 FBC M.
  
 2) M-1: 2ND REQUEST TO PROVIDE SYMBOLS TO INDICATE THE
 LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE
 AIR HANDLER SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION
 606.2.1 FBC M. THE DETECTORS SHALL BE LOCATED IN THE
 SUPPLY SYSTEMS.
  
 3) PLEASE PROVIDE AC CALCULATIONS CONSISTENT WITH THE
 PROPOSED USE OF THE SPACES. THE SUBMITTED CALCULATIONS
 DO NOT INCLUDE LOADS FROM LIGHTING, OCCUPANTS, OFFICE
 EQUIPMENT, VENTILATION ETC., AND AT A TOTAL COOLING
 LOAD OF 62921 BTUH, THE SYSTEMS SELECTED WOULD BE
 OVERSIZED- SEE SECTION C403.2.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  