Plan Review Notes
Plan Review Notes For Permit 19061087
Permit Number 19061087
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-10 13:39:051ST REVIEW: 19061087
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 ACCESSIBILITY REQUIREMENTS FBC ACC 2017 6TH EDITION
  
 602 DRINKING FOUNTAINS
 A)602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR
 FLOOR OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR
 A FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 B)602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 C)602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 604 WATER CLOSETS AND TOILET COMPARTMENTS
 A)604.2 LOCATION. THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 B)604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 C)604.3.2 OVERLAP.THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
 D)604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION
 604.5 GRAB BARS.
 A)604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
 B)604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
 C)609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
 606 LAVATORIES
 A)606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 B)606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
  
 2.TWO BATHROOMS ARE REQUIRED PER FBC PL 403.2 SEPARATE
 FACILITIES. WHERE PLUMBING FIXTURES ARE REQUIRED,
 SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 3. A DRINKING FOUNTAIN IS REQUIRED AND SHALL COMPLY
 WITH ACCESSIBILITY. PER FBC PL TABLE 403.1
  
 4. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 5. SHT. P-1 THE SANITARY ISOMETRIC DRAWING SHOWS A VENT
 CONNECTED TO THE TOP OF THE TOILET THIS IS NOT AN
 APPROVED VENTING METHOD PLEASE REMOVE, THE VENT FROM
 THE LAVATORY SHALL VENT THE TOILETS PER FBC PL 912.1
  
 6.TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 7. SHT. LS-1 AND M-1 IS SHOWING A PARTION AND WALL HUNG
 SINK NEXT TO THE TOILET THE RST OF THE PLAN DOES NOT
 SHOW THIS PLEASE CLARIFY
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711