| 2019-07-16 16:09:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19061087 |
| | 9/16/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: THE VENTILATION CALCULATIONS ARE |
| | INDICATING OFFICE SPACES, HOWEVER THE LARGE OPEN SPACE |
| | IS IDENTIFED AS A "FUTURE TENANT SPACE". PLEASE SEE THE |
| | BUILDING REVIEW COMMENTS AND PROVIDE THE CORRECT |
| | IDENTIFICATION AND USE OF THIS SPACE IN ORDER TO |
| | PROVIDE ADEQUATE VENTILATION PER TABLE 403.3.1.1 FBC M. |
| | |
| | 2) M-1: PROVIDE SYMBOLS TO INDICATE THE LOCATIONS OF |
| | THE REQUIRED DUCT SMOKE DETECTORS IN THE AIR HANDLER |
| | SUPPLY SYSTEMS- SEE NOTE #5 AND SECTION 606.2.1 FBC M. |
| | |
| | 3) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| | HANDLERS- SECTION 307.2.1 FBC M. |
| | |
| | 4) SHOW THE LOCATIONS OF THE AC CONDENSERS AND PROVIDE |
| | ENGINEERED INSTALLATION DETAILS- SECTION 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |