| 2019-06-25 14:41:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET O2 - THERE ARE INDICATIONS OF FIRE SPRINKLER |
| | HEAD LOCATIONS; HOWEVER, SOME LOCATIONS DO NOT APPEAR |
| | TO BE CODE COMPLIANT. |
| | |
| | ADDITIONALLY, THERE ARE NO INDICATIONS OF THE POSITION |
| | OF EXISTING HEADS VS INSTALLED HEADS. I.E UPRIGHT VS |
| | PENDANT. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| | AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE. |
| | |
| | |
| | |
| | 2) SHEET E 1 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| | DEVICES EXISTING NOR PROPOSED. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE. |
| | |
| | |
| | |
| | 3) SHEET M 1 - THERE ARE INDICATIONS OF A/C UNITS WITH |
| | OVER 2,000 CFM WITH NO DUCT DETECTORS INDICATED THAT |
| | ARE REQUIRED TO BE TIED INTO THE FIRE ALARM SYSTEM. |
| | |
| | PER NFPA 90 A , CHAPTER 6 CONTROLS |
| | 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL. |
| | 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE |
| | TESTED AT LEAST ANNUALLY. |
| | 6.4.2* LOCATION. |
| | 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR |
| | DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: |
| | (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY |
| | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A |
| | CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN) |
| | (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON |
| | RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR |
| | INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A |
| | CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND |
| | SERVING MORE THAN ONE STORY |
| | |
| | 6.4.3* FUNCTION. |
| | 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 |
| | SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON |
| | DETECTING THE PRESENCE OF SMOKE. |
| | |
| | 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE |
| | AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A |
| | BUILDING, THE SMOKE DETECTORS REQUIRED BY THE |
| | PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE |
| | FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS |
| | OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING |
| | CODE. |
| | |
| | PLEASE REVIEW AND PROVIDE DESIGN DETAIL AND AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT OR JUSTIFY WHY NOT |
| | WITH SPECIFIC NARRATIVE AND CODE REFERENCES. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |