Plan Review Notes
Plan Review Notes For Permit 19061087
Permit Number 19061087
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-25 14:41:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET O2 - THERE ARE INDICATIONS OF FIRE SPRINKLER
 HEAD LOCATIONS; HOWEVER, SOME LOCATIONS DO NOT APPEAR
 TO BE CODE COMPLIANT.
  
 ADDITIONALLY, THERE ARE NO INDICATIONS OF THE POSITION
 OF EXISTING HEADS VS INSTALLED HEADS. I.E UPRIGHT VS
 PENDANT.
  
 PLEASE PROVIDE DETAILS.
  
 FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE.
  
  
  
 2) SHEET E 1 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES EXISTING NOR PROPOSED.
  
 PLEASE PROVIDE DETAILS.
  
 FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OF THE ABOVE.
  
  
  
 3) SHEET M 1 - THERE ARE INDICATIONS OF A/C UNITS WITH
 OVER 2,000 CFM WITH NO DUCT DETECTORS INDICATED THAT
 ARE REQUIRED TO BE TIED INTO THE FIRE ALARM SYSTEM.
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 PLEASE REVIEW AND PROVIDE DESIGN DETAIL AND AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT OR JUSTIFY WHY NOT
 WITH SPECIFIC NARRATIVE AND CODE REFERENCES.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  