2019-07-17 15:53:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 LOAD CALCULATION FOR THE SPACE MISSING THE LIGHTING
 LOADS.
  
 NEED FAULT CURRENT CALCULATION FOR 400A WITH NEW LOADS
 ADDED.
  
 RISER SHOWS A 200 AMPERE METERCAN ON A 400A SERVICE.
  
 EXAM ROOMS WHAT KIND OF EXAMS, DO YOU ADMINISTER ANY
 MEDICATION OR USE MEDICAL EQUIPMENT?