| Plan Review Notes For Permit 19061087 |
| Permit Number |
19061087 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-17 15:53:21 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | LOAD CALCULATION FOR THE SPACE MISSING THE LIGHTING | | | LOADS. | | | | | | NEED FAULT CURRENT CALCULATION FOR 400A WITH NEW LOADS | | | ADDED. | | | | | | RISER SHOWS A 200 AMPERE METERCAN ON A 400A SERVICE. | | | | | | EXAM ROOMS WHAT KIND OF EXAMS, DO YOU ADMINISTER ANY | | | MEDICATION OR USE MEDICAL EQUIPMENT? |
|