2019-10-22 09:54:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD BUILDING REVIEW DENIED:
  
 1A) FAILED: FEMA TECHNICAL BULLETIN 2; THE NEW FINISH
 FLOOR ELEVATION DETAIL INDICATES 14' 1/4" AT TOP OF
 SUB-FLOOR. THIS ELEVATION IS NOT ACCEPTABLE DUE TO THE
 FLOOR FRAMING NOT MEETING THE REQUIREMENTS OF FLOOD
 DAMAGE-RESISTANT MATERIALS. A NEW ELEVATION CERTIFICATE
 WILL HAVE TO BE SUBMITTED IF ELEVATIONS ARE ADJUSTED.
 1B) FAILED: FBC B 107.2.1 PROVIDE ANCHORING DETAILS FOR
 THE EXTERIOR A/C RACKS (MEETING 14.00' ELEVATION
 REQUIREMENT). THE NEW ELEVATION CERTIFICATE (SECTION
 C2-E) WILL HAVE TO INCLUDE ELEVATION OF EQUIPMENT.
 2.) APPROVED.
 3.) APPROVED.
 4.) APPROVED.
 5.) APPROVED.
 6.) APPROVED.
 7.) APPROVED.
 8.) APPROVED.
 9.) APPROVED.
  