| Plan Review Notes For Permit 19061078 |
| Permit Number |
19061078 |
|
| Review Stop |
NFIP |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-10-22 09:56:25 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | NFIP REVIEW DENIED: | | | | | | | | | 1.) FAILED: FEMA TECHNICAL BULLETIN 2; THE NEW FINISH | | | FLOOR ELEVATION DETAIL INDICATES 14? 1/4" AT TOP OF | | | SUB?FLOOR. THIS ELEVATION IS NOT ACCEPTABLE DUE TO THE | | | FLOOR FRAMING NOT MEETING THE REQUIREMENTS OF FLOOD | | | DAMAGE?RESISTANT MATERIALS. A NEW ELEVATION CERTIFICATE | | | WILL HAVE TO BE SUBMITTED IF ELEVATIONS ARE ADJUSTED. | | | | | | 2.) FAILED: FBC B 107.2.1 PROVIDE ANCHORING DETAILS FOR | | | THE EXTERIOR A/C RACKS (MEETING 14.00? ELEVATION | | | REQUIREMENT). | | | THE NEW ELEVATION CERTIFICATE (SECTION | | | C2?E) WILL HAVE TO INCLUDE ELEVATION OF EQUIPMENT. | | | | | | | | | |
|