Plan Review Notes
Plan Review Notes For Permit 19061078
Permit Number 19061078
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-25 15:05:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 02 - THERE IS AN INDICATION UNDER THE CALL-OUT
 DRAWING OF THE MTAL STUD PARTITION, "REFER TO FINSIH
 SCHEDULE FOR APPLIED FINISHES."
  
 THERE IS NO FINISH SCHEDULE FOR REFERRING.
  
 PER NFPA 101, CH 38, NEW BUSINESS OCCUPANCIES
  
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH
 SECTION 10.2 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN EXIT ACCESS
 CORRIDORS.
 38.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASS A,
 CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE SPECIFIED
 IN
 38.3.3.2.1.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
  
 2) SHEET 00 - THERE IS AN INDICATION UNDER D. FLOORING,
 "SEE SCHEDULE FOR ALLOWANCES FOR NEW FLOORING"
  
 THERE IS NO SCHEDULE FOR REFERRING.
  
 PER NFPA 101, CH 38, NEW BUSINESS OCCUPANCIES
  
 38.3.3.3 INTERIOR FLOOR FINISH.
 38.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 38.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES
 SHALL BE CLASS
 I OR CLASS II.
 38.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  