Plan Review Notes
Plan Review Notes For Permit 19061078
Permit Number 19061078
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-08 15:58:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19061078
 ADD: 5800 CORPORATE WAY
 CONT: GEN-X CONSTRUCTION, INC.
 TEL: 561-963-4490
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 08/2019
 ACTION: DENIED
  
 1) THE SITE PLAN CREATED BY ARCHITECT JEFFREY ORNSTEIN
 IDENTIFIES THE BUILDING FOR THE PROPOSED PERMITTED WORK
 AS ANNEX SUBJECT ONE STORY BUILDING WITH A FINISH FLOOR
 ELEVATION 15.5 FEET. PLEASE PROVIDE A CURRENT SURVEY
 FOR THIS BUILDING IN NAVD 88. THIS BUILDING IS IN AN AE
 FLOOD ZONE WITH A BFE OF 12.0 FEET NAVD88.
 THE CITY HAS GONE THROUGH A SERIES OF FREEBOARD CHANGES
 TO KEEP UP WITH THE FBC-BUILDING CODE PLUS INCREASE OUR
 FREEBOARD TO 2 FEET ABOVE THE BASE FLOOD.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF
 PERMIT APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 THE PROPOSED IMPROVEMENT ($138,917 PLUS $448,181.00
 DOLLARS, OF LAST 5 YEARS OF IMPROVEMENTS ) APPEARS TO
 BE A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE
 STRUCTURE ($704,160.00). IF THIS IS A SUBSTANTIAL
 IMPROVEMENT. THE STRUCTURE IS TO BE BROUGHT INTO
 COMPLIANCE (BFE 14.0? NAVD88 FOR THE LOWEST FINISHED
 FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT CAN
 PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE
 PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL
 BULLETIN 758 SECTION 4.5:
 HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2
 5045-2915/P_758_COMPLETE_R3.PDF
  
 PLEASE NOTE THE VALUE OF THE STRUCTURES FROM THE
 PROPERTY APPRAISER?S OFFICE IS FOR BOTH BUILDINGS AND
 THE MAJORITY OF THE LAST 5 YEARS IS ON THE LARGER
 BUILDING WHICH IS OUT OF THE FLOOD ZONE. WHAT WE NEED
 IS THE ASSESSED VALUE FOR THE ANNEXED BUILDING PLUS A
 NEW SURVEY IN NAVD88 TO DETERMINE IF THIS BUILDING
 COMPLIES WITH THE FEMA REGULATIONS. SINCE THE ANNEXED
 BUILDING IS IN AN AE FLOOD ZONE WITH A BFE OF 12.0 FT.
 NAVD 88 A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 2) NEITHER SHEET 00 OR 01 INDICATE THE FOLLOWING
 MISSING INFORMATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 504.4 & TABLE 506.2).
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
  
 3) SHEET 01 INDICATES THE REPLACEMENT OF ALL WINDOWS
 AND DOORS BUT NO WIND DESIGN CRITERIA HAS BEEN GIVEN.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR NOA 14-0513.03 NOT REVIEWED BY THE
 DESIGNER OF RECORD.
 (B) WINDOWS NOA 17-0630.08 NOT REVIEWED BY THE DESIGNER
 OF RECORD.
  
 5) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8) SHEET 01 THE RESTROOM BACK WALL MEASUREMENT SHOWS 7
 FEET WHEREAS THE DETAIL OF THE RESTROOM SHOWS A
 BACKWALL MEASUREMENT OF 7 FEET 6 INCHES. DISCREPANCY IN
 PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) SHEET 02 LOUNGE AREA DETAIL SHOWS THE TOP OF THE
 CABINETS AT 36 INCHES IN HEIGHT. PLEASE SHOW COMPLIANCE
 WITH 2017 ACCESS. CODE SECTION SINKS. 2017
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  