| Notes |
| Date |
Text |
| 2019-06-25 10:35:39 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) PLUMBING ISOMETRIC SHOW THE BAR SINK BEING VENTED BY | | | AAV. EACH BUILDING DRAIN SHALL HAVE A VENTTHAT ENTENDS | | | TO THE OUTDOORS. REFER TO FBCR-P3102.1 | | | | | | 2) PLUMBING ISOMETRIC DOES NOT SHOW THE BATHROOM SINK | | | AS BEING VENTED. PROVIDE A VENT. FBCR-P 3101.2.1 | | | | | | 3) PROVIDE SHOWER PAN DETAIL SHOWING MATERIAL TO BE | | | USED AND FLOORING PRE PITCH IF NOT RECESSED. FBC | | | 107.2.1 | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|