Plan Review Notes
Plan Review Notes For Permit 19061015
Permit Number 19061015
Review Stop G
Sequence Number 1
Notes
Date Text
2019-06-25 10:24:50GAS 1ST REVIEW**DENIED**
  
 1) PROVIDE INSTALLATION MANUAL FOR THE TANKLESS WATER
 HEATER. FBC 107.2.1
  
 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING
 APPLIANCES.FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) THE 1 1/4" LINE APPEARS TO BE UNDERGROUD AND SCH 40
 METAL PIPE AS THE ONLY SIZING CHART PROVIDED. SCH 40
 METAL PIPING IS NOT PERMITTED UNDER GROUND. PLEASE
 CLARIFY. FBC-G 404.11, 404.11.1, 404.11.2
  
 4) PROVIDE MOUNTING DISTANCE OF TANKLESS WATER HEATER,
 FROM CORNER WALL, OVERHANG, AND FROM ANY DOOR OR WINDOW
 THAT OPENS. FBC 107.2.1PLEASE VERIFY WITH INSTALLATION
 MANUAL FOR REQUIRED DISTANCES.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved