| Plan Review Notes For Permit 19061006 |
| Permit Number |
19061006 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-22 13:48:52 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW OF THIS SUBMITTAL IS DENIED. | | | | | | FBC B 107. | | | 1. THE ERECTION OF THE MEZZANINE STRUCTURAL FRAMING | | | MEMBERS IS NOT SPECIFIC AS TO THE CONFLICT, OBSERVED | | | ON-SITE, OF THE STRUCTURAL DRAWING DETAILS WITH THE | | | FRAMING MEMBERS THAT WERE ERECTED. | | | THE FLAT/HORIZONTAL LEG OF THE STEEL JOISTS THAT BEAR | | | AND ARE TO BE WELDED TO THE TOP FLANGE OF THE | | | SUPPORTING BEAMS DID NOT EXIST AS PART OF THE JOISTS AT | | | TIME OF INSPECTION. SEE, INCLUDED IN THE PERMIT | | | PACKAGE, A COPY OF THE AREA OF CONCERN. | | | PLEASE PROVIDE BY DESIGNER OF RECORD: 1. PHOTOS AND | | | SPECIFIC APPROVAL OF REPAIR TO JOISTS; AND 2. APPROVAL | | | OF ERECTION AND ALL WELDED CONNECTIONS. | | | | | | 2. THE SIGNATURES ON THE SUBMITTED INSPECTION REPORTS | | | WERE NOT SIGNED IN ACCORDANCE WITH THE PROVISIONS OF | | | SECTION 471.025,F.S. AND RULE 61G15-23.001 OF THE | | | FLORIDA ADMINISTRATIVE CODE. | | | AS THESE DOCUMENTS WERE SUBMITTED ON PAPER, A DIGITAL | | | SIGNATURE IS NOT APPLICABLE IN THIS CASE. |
|