Plan Review Notes
Plan Review Notes For Permit 19060948
Permit Number 19060948
Review Stop E
Sequence Number 1
Notes
Date Text
2019-06-21 14:30:03FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E2.0 FLOATING MIXERS AND CONTROLLERS NEED CUT
 SHEETS ON THIS EQUIPMENT.
  
 2) PAGE E2.1MCC-1 SHOW BUSS TAP PLEASE HAVE FIELD
 EVALUATION FOR THIS WORK BY A NATIONALY RECOGNIZED
 TESTING LAB. PER 110.3(B) LISTING AND USE.
 PLEASE INDICATE NEW EQUIPMENT ON PLAN.
  
 3) PAGE E2.2 NEED TO SUBMIT CUT SHEETS ON CABLES USED
 FOR MIXERS.