| Plan Review Notes For Permit 19060948 |
| Permit Number |
19060948 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-21 14:30:03 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PAGE E2.0 FLOATING MIXERS AND CONTROLLERS NEED CUT | | | SHEETS ON THIS EQUIPMENT. | | | | | | 2) PAGE E2.1MCC-1 SHOW BUSS TAP PLEASE HAVE FIELD | | | EVALUATION FOR THIS WORK BY A NATIONALY RECOGNIZED | | | TESTING LAB. PER 110.3(B) LISTING AND USE. | | | PLEASE INDICATE NEW EQUIPMENT ON PLAN. | | | | | | 3) PAGE E2.2 NEED TO SUBMIT CUT SHEETS ON CABLES USED | | | FOR MIXERS. |
|