| Notes |
| Date |
Text |
| 2019-07-05 09:24:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | COMMENTFROM PREVIOUS LIST: | | | | | | 1. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE | | | NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON | | | SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF | | | USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON | | | W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). | | | | | | 2ND REVIEW, THE .9 FACTOR WAS NOT APPLIED TO THE 12" | | | ANCHOR SPACING FOR TAPCON W/ADVANCED THREDFORM | | | TECHNOLOGY FASTENER. | | | | | | ALSO NOTE THAT ANCHOR TYPES A, D, U ARE SPECIFIED ON | | | THE INSTALLATION SCHEDULE BUT A, H AND D ARE | | | HIGHLIGHTED; PLEASE CORRELATE. | | | | | | 2. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | | | | | | | |
|