2019-12-17 10:04:064TH REVIEW FBC-2017 MECHANICAL
 PERMIT #19060896
 2/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.1: THE 21 SF. GRAVITY VENTILATOR OPENING IS
 UNDERSIZED FOR THE TOTAL NUMBER OF DRYERS TO BE
 INSTALLED. THERE ARE 12- T50X2 UNITS (24 TUMBLERS) PLUS
 2- T80 UNITS (2 TUMBLERS)= (26 TUMBLERS) X (1.5 SF.
 EACH) = 39 SF. OF FREE AIR OPENING REQUIRED.
  
 2) PLEASE PROVIDE A DUPLICATE COPY OF THE
 MANUFACTURER'S SPECS FOR THE X2 DRYERS- THERE IS ONLY
 ONE COPY SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  