| 2019-12-16 15:03:20 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19060896 |
| | ADD: 1242 PALM BEACH LAKES |
| | CONT: DCOTA CONTRACTING INC. |
| | TEL: 561-718-6565 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: MON. DEC. 16/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THIS SUBMITTAL THE PLANS HAVE NOT BEEN COLLATED |
| | CORRECTLY, MISSING THE COVERSHEET, SHEET 1.1 THE FLOOR |
| | DEMOLITION PLAN. THERE IS NOW A SHEET 2.0 NOT FOUND ON |
| | THE ORIGINAL INDEX PLUMBING PLAN, WATER PLAN. |
| | 2) ON THE ORIGINAL REVIEW THE INDEX SHEET INDICATED |
| | SHEET 2.1 WAS THE LIFE SAFETY PLAN WITH PROJECT DATA, |
| | SHEET 2.1 IS NOW THE GAS RISER AND SANITARY RISER |
| | SHEET. |
| | 3) BUILDING/ STRUCTURAL DETAILS THAT WERE ON THE VOIDED |
| | SHEET 4.1 ARE NOW ON SHEET 4.0 A VERY LIGHT GRAY LINE |
| | DRAWING. WILL NOT MEET THE STANDARDS TO BE SCANNED IN |
| | FOR RECORD RETENTION. |
| | 107.2.1.3 QUALITY OF BUILDING PLANS. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | 4) ADDITIONAL COMMENTS FROM THE 1ST REVIEW THAT CANNOT |
| | BE FOUND ON THE CURRENT SET OF PLANS. |
| | |
| | |
| | 1) SHEET 2.1 THE LIFE SAFETY FLOOR PLAN. |
| | |
| | 1C) PLEASE CORRECT THE STATEMENT, PLANS COMPLY WITH THE |
| | 2014 FBC. DEC. 31/ 2017 THE 2017 FBC FAMILY OF CODES |
| | WAS ADOPTED STATEWIDE. |
| | |
| | 1D) SHEET 2.1 SHOWS THE BACK DOOR BEING INFILLED FROM 6 |
| | FEET TO 4 FOOT 4 INCHES IN WIDTH. SHEET 4.1 HAS A |
| | DETAIL FOR THE WINDOW INFILL DETAIL ABOVE THE DOOR BUT |
| | THERE IS NO DETAIL FOR THE DOOR INFILL. ADDITIONAL |
| | INFORMATION IS REQUIRED. 107.2.1.2. |
| | |
| | 1E) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW |
| | DOOR OPENING. 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1E)(1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| | GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND |
| | SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 1E)(2.) RISK CATEGORY. |
| | |
| | 1E)(3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF |
| | MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE |
| | 1609.7.2. HEIGHT AND EXPOSURE. |
| | |
| | 1E)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1E)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 1F) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | |
| | 1G) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 1H) IF THE NEW DOOR IS GLAZED. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 1I) THE SHEET 2.1 INDICATES ONLY ONE RESTROOM. PLEASE |
| | SEE THE 2017 FBC-B TABLE 2902.1 REQUIRING 2 RESTROOMS. |
| | SECTION 2902.2 OF THE FBC-B SEPARATE FACILITIES |
| | EXCEPTION 2 ONLY ALLOWS FOR A SINGLE RESTROOM WHEN |
| | THERE IS A TOTAL OCCUPANT LOAD OF 15 OR FEWER EMPLOYEES |
| | AND CUSTOMERS. 2 RESTROOMS ARE REQUIRED. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | JAMES A. WITMER BN, PX, CBO |