Plan Review Notes For Permit 19060896
Permit Number 19060896
Review Stop I
Sequence Number 3
Notes
Date Text
2019-11-05 16:19:58RESUB ROUTED TO CCOLE
2019-11-05 14:39:33PLUMBING PLANS HAVE ADDED ELECTRIC WATER HEATER. DEVICE
 WAS ADDED AFTER PREVIOUS ELECTRICAL REVIEWS. CURRENT
 REVIEWED ELECTRICAL PLANS DO NOT REFLECT THE DEVICE.
2019-11-05 11:31:51RESUB ROUTED TO JESMITH