Plan Review Notes
Plan Review Notes For Permit 19060896
Permit Number 19060896
Review Stop G
Sequence Number 3
Notes
Date Text
2019-12-24 11:13:433RD REVIEW: 19060896
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SHT. 2.0 ON THE WATER AND GAS PLAN IT LIST 12 OF THE
 T-50 THE PLAN ONLY SHOWS 10 IF 2 OF THEM ARE FUTURE
 PLEASE SHOW LOCATION ON PLAN AND LABEL AS FUTURE. PER
 WPB AMEND TO FBC PL 107.2.1
  
 2. SHT. 2.0 THE NOTE ON THE WATER GAS PLAN LIST T-50
 BUT THE PLAN SHOWS T-50X2 PLEASE CLARIFY. PER WPB AMEND
 TO FBC PL 107.2.1
  
 3. SHT. 2.1 ON THE GAS RISER THE SIZING ON THE 2LB
 PIPING IS SHOWN AT THE METER AS 11/4" FOR THE FIST
 SECTION 11/2 FOR THE 40' SECTION AND 2" ON THE 18'
 SECTION PLEASE CLARIFY. PER WPB AMEND TO FBC PL 107.2.1
  
 4.SHT. 3.1 APPEARS TO BE A PREVIOUS VERSION OF THE GAS
 RISER PLEASE REMOVE PLANS THAT ARE TO BE VOIDED AND
 HAVE BEEN REVISED. PER WPB AMEND TO FBC PL 107.2.1
  
 5. COMBUSTIONS AIR PLEASE SEE COMMENTS ON MECHANICAL
 REVIEW ALSO PROVIDE DIMENSIONS OF THE SPACE ABOVE THE
 BATHROOMS BELOW THE PENTHOUSE VENTILATOR. PER WPB AMEND
 TO FBC PL 107.2.1
 I BELIEVE YOUR CALCULATIONS USING THE MAKE UP AIR
 LISTED IN THE MANUFACTURE SPECIFICATIONS MAYBE
 INCORRECT THE MAKE AIR IS THE AIR REPLACING THE AIR
 SUCKED OUT OF THE SPACE USED IN THE DRYING PROCESS AND
 EXHAUSTED TO THE OUTSIDE THE COMBUSTION AIR IS THE
 AMOUNT OF AIR NEEDED TO BURN THE FUEL COMPLETELY THIS
 IS IS SEPARATE FROM ANY MAKE UP AIR AND WITHOUT THE
 PROPER AMOUNT OF COMBUSTION AIR THERE CAN BE INCOMPLETE
 BURN RESULTING IN EXCESS CARBINE MONOXIDE. USING THE
 STANDARD METHOD OUT OF THE CODE OF 50 CUBIC FT PER 1000
 RESULTS IN 151,000 CUBIC FT OF COMBUSTION AIR WHICH CAN
 COME FROM THE SPACE THE DRYERS ARE IN AND IF THAT IS
 NOT ENOUGH THEN YOU CAN BRING IN AIR FRO THE OUTSIDE.
 PER FBCFG 304.5.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH