| 2019-12-24 11:13:43 | 3RD REVIEW: 19060896 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. SHT. 2.0 ON THE WATER AND GAS PLAN IT LIST 12 OF THE |
| | T-50 THE PLAN ONLY SHOWS 10 IF 2 OF THEM ARE FUTURE |
| | PLEASE SHOW LOCATION ON PLAN AND LABEL AS FUTURE. PER |
| | WPB AMEND TO FBC PL 107.2.1 |
| | |
| | 2. SHT. 2.0 THE NOTE ON THE WATER GAS PLAN LIST T-50 |
| | BUT THE PLAN SHOWS T-50X2 PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC PL 107.2.1 |
| | |
| | 3. SHT. 2.1 ON THE GAS RISER THE SIZING ON THE 2LB |
| | PIPING IS SHOWN AT THE METER AS 11/4" FOR THE FIST |
| | SECTION 11/2 FOR THE 40' SECTION AND 2" ON THE 18' |
| | SECTION PLEASE CLARIFY. PER WPB AMEND TO FBC PL 107.2.1 |
| | |
| | 4.SHT. 3.1 APPEARS TO BE A PREVIOUS VERSION OF THE GAS |
| | RISER PLEASE REMOVE PLANS THAT ARE TO BE VOIDED AND |
| | HAVE BEEN REVISED. PER WPB AMEND TO FBC PL 107.2.1 |
| | |
| | 5. COMBUSTIONS AIR PLEASE SEE COMMENTS ON MECHANICAL |
| | REVIEW ALSO PROVIDE DIMENSIONS OF THE SPACE ABOVE THE |
| | BATHROOMS BELOW THE PENTHOUSE VENTILATOR. PER WPB AMEND |
| | TO FBC PL 107.2.1 |
| | I BELIEVE YOUR CALCULATIONS USING THE MAKE UP AIR |
| | LISTED IN THE MANUFACTURE SPECIFICATIONS MAYBE |
| | INCORRECT THE MAKE AIR IS THE AIR REPLACING THE AIR |
| | SUCKED OUT OF THE SPACE USED IN THE DRYING PROCESS AND |
| | EXHAUSTED TO THE OUTSIDE THE COMBUSTION AIR IS THE |
| | AMOUNT OF AIR NEEDED TO BURN THE FUEL COMPLETELY THIS |
| | IS IS SEPARATE FROM ANY MAKE UP AIR AND WITHOUT THE |
| | PROPER AMOUNT OF COMBUSTION AIR THERE CAN BE INCOMPLETE |
| | BURN RESULTING IN EXCESS CARBINE MONOXIDE. USING THE |
| | STANDARD METHOD OUT OF THE CODE OF 50 CUBIC FT PER 1000 |
| | RESULTS IN 151,000 CUBIC FT OF COMBUSTION AIR WHICH CAN |
| | COME FROM THE SPACE THE DRYERS ARE IN AND IF THAT IS |
| | NOT ENOUGH THEN YOU CAN BRING IN AIR FRO THE OUTSIDE. |
| | PER FBCFG 304.5.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |