| 2019-09-17 14:20:24 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. 2ND REQUEST; PER FBC ACC 609.4, GRAB BARS SHALL BE |
| | INSTALLED IN HORIZONTAL POSITION 33 INCHES MINIMUM/36 |
| | INCHES MAXIMUM ABOVE FINISHED FLOOR TO TOP OF THE |
| | GRIPPING SURFACE, NOT TO CENTER. PER WPB FBC 107.2.1, |
| | CORRECT "TOILET ACCESSORY SCHEDULE" ON PLAN SHT. 2.1 |
| | AND "TYPICAL TOILET ROOM ELEVATIONS" ON PLAN SHT. 3.1. |
| | 2. 2ND REQUEST; RE: "TYPICAL TOILET ROOM ELEVATIONS" ON |
| | PLAN SHT. 3.1. |
| | |
| | A. WATER CLOSET SHALL BE 16 INCHES MINIMUM/18 INCHES |
| | MAXIMUM FROM SIDE WALL TO CENTER PER FBC ACC 604.2. |
| | B. REAR GRAB BAR SHALL BE 12 INCHES MINIMUM FROM CENTER |
| | OF WATER CLOSET TOWARD SIDEWALL AND 24 INCHES MINIMUM |
| | FROM CENTER OF WATER CLOSET TOWARD OPEN SIDE PER FBC |
| | ACC 604.5.2. |
| | |
| | 3. 2ND REQUEST; PER WPB FBC 107. 2.1, PROVIDE PRODUCT |
| | SPECS FOR LINT INTERCEPTORS (SEE NOTE ON PLAN SHT. |
| | 3.1). |
| | 4. 2ND REQUEST; PER WPB FBC 107. 2.1, PROVIDE DETAIL OF |
| | WASHER CONNECTION TO INTERCEPTOR AND INTERCEPTOR |
| | DISCHARGE |
| | 5. 2ND REQUEST; PER WPB FBC 107. 2.1, PROVIDE PIPING |
| | DETAIL FOR TYPICAL BANK OF LINT INTERCEPTORS. INCLUDE |
| | SIZING AND VENTING |
| | 6. 2ND REQUEST; PER PROVIDE TEMPERED WATER FOR |
| | LAVATORY/LAVATORIES CONFORMING TO ASSE 1070 PER FBC PL |
| | 416.5. PROVIDE SPEC FOR SAME PER WPB FBC 107.2.1. |
| | 7. 2ND REQUEST; PER WPB FBC 107.2.1, PROVIDE A DETAIL |
| | FOR THE TWO (2) TANKLESS WATER HEATERS SHOWING PIPING |
| | AND VALVE ARRANGEMENT. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | NEW GAS PLANS WERE NOT SUBMITTED FOR REVIEW AT THIS |
| | TIME |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19060896 1242 PALM BEACH LAKES BLVD |
| | |
| | |