| Date |
Text |
| 2019-09-18 15:09:45 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19060896 |
| | 9/18/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4.1: THE REQUIRED MAKEUP AIR FOR THE GAS |
| | DRYERS HAS NOT BEEN PROVIDED AS REQUIRED BY THE |
| | SUBMITTED MANUFACTURER'S SPECIFICATIONS- SEE PAGES |
| | 15-16 OF THE SPECS AND REVISE THE PLAN TO SHOW |
| | COMPLIANCE AND INCLUDE CALCULATIONS. |
| | |
| | 2) SHEET 4.1: REFER TO PAGES 17-18 OF THE SUBMITTED GAS |
| | DRYER SPECIFICATIONS AND PROVIDE DIAGRAMS OF THE |
| | EXISTING DRYER VENT SYSTEMS TO VERIFY COMPLIANCE WITH |
| | THE SPECS. INDICATE IN THE DIAGRAMS THE TYPES AND SIZES |
| | OF VENTS, NUMBER OF ELBOWS, LENGTH OF VENT RUNS, |
| | TERMINATION HEIGHTS ABOVE THE ROOF, AND CLEARANCES TO |
| | COMBUSTIBLES. |
| | |
| | 3) SHEET 4.1: THE MODEL NUMBERS OF THE DRYERS ARE NOT |
| | LEGIBLE ON THE PLAN. PLEASE ENLARGE THE PRINT- SECTION |
| | 107.2 WPB. |
| | |
| | 4) THE COMPLIANCE DATA FOR THE10-TON RTU AS SHOWN IN |
| | THE ENERGY COMPLIANCE REPORT DOES NOT MATCH THE UNIT |
| | SPECS- 120,000 BTUH COOLING, 34121 BTUH HEATING, AND |
| | 11.3 EER. PLEASE NOTE EFFICENCIES FOR 10-TON UNITS ARE |
| | RATED PER EER NOT SEER- SEE TABLE C403.2.3(1) FBC EC. |
| | .PLEASE CORRECT THE REPORT TO MATCH THE SCHEDULE AND |
| | SPECS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |