| 2019-11-05 15:55:01 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | GAS COMMENTS: DENIED |
| | A SEPARATE GAS PERMIT IS REQUIRED |
| | |
| | 1. ENGINEER HAS NOW PROVIDED GAS TANKLESS WATER HEATERS |
| | IN AN OUTDOOR SETTING. SUBMITTED SPECIFICATIONS ARE FOR |
| | INDOORS. PLEASE PROVIDE CORRECT SPECIFICATION SHEETS TO |
| | MATCH OUTDOOR APPLICATION. |
| | 2. PLAN SHEET 2.1: GAS LOAD CALCULATIONS SHOULD BE |
| | 2,558,000 BTUS AT 2 PSI FARTHEST DISTANCE FROM METER TO |
| | MP REGULATOR IN THE CEILING AT THE BEGINNING OF THE |
| | DRYERS. PLEASE SIZE ACCORDINGLY IN ACCORDANCE WITH FBC |
| | FG TABLE 402.4(5), CALLING OUT THE DISTANCE. |
| | 3. PLAN SHEET 2.1: GAS LOAD CALCULATIONS SHOULD BE |
| | 2,160,000 BTUS AT LESS THAN 2 PSI FARTHEST DISTANCE |
| | FROM MP REGULATOR IN THE CEILING AT THE BEGINNING OF |
| | THE DRYERS TO THE FARTHEST DRYER GAS CONNECTION. PLEASE |
| | SIZE ACCORDINGLY IN ACCORDANCE WITH FBC FG TABLE |
| | 402.4(4), CALLING OUT THE DISTANCE. |
| | 4. PLAN SHEET 2.1: GAS LOAD CALCULATIONS ARE 398,000 |
| | BTUS AT LESS THAN 2 PSI FARTHEST DISTANCE FROM MP |
| | REGULATOR TO THE FARTHEST GAS HEATER CONNECTION. PLEASE |
| | SIZE ACCORDINGLY IN ACCORDANCE WITH FBC FG TABLE |
| | 402.4(4), CALLING OUT THE DISTANCE. |
| | 5. PLAN SHEET 2.1: CLEARLY SHOW ON THE ISOMETRIC |
| | DRAWING THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC |
| | FG, SECS. 402.4.1, 402.4.2. SHOW ALL SIZING, VALVES AND |
| | PRESSURE REGULATORS. IDENTIFY TYPE OF MATERIAL BEING |
| | USED. |
| | 5. PROVIDE SPECIFICATION FOR MP REGULATORS FOR WATER |
| | HEATERS AND DRYERS. MP REGULATOR SHALL BE RATED FOR |
| | OUTDOORS. |
| | 6. PLAN SHEET 3.1 ALSO NOTES GAS RISER DIAGRAM WHICH IS |
| | STAMPED FROM AN EARLIER REVIEW. PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY. REMOVE ANY RISERS OR INFORMATION THAT |
| | IS NO LONGER PART OF THE PROJECT AND RESUBMIT. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19060896 1242 PALM BEACH LAKES BLVD |
| | |
| | |