| 2019-07-02 15:46:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. OCCUPANT LOAD OF 18 IS LESS THAN 100? GROSS/1882 SQ. |
| | FT. SHOULD BE 19. FBC PL 403.2 REQUIRES TWO TOILET |
| | ROOMS. IF USING FBC EX ALTERATIONS LEVEL 2 SECTION 810 |
| | TO JUSTIFY THE LACK OF THE SECOND TOILET ROOM, THEN |
| | PROVIDE DETAILED INFORMATION AND CALCULATIONS AS TO HOW |
| | THIS WOULD BE ACHEIVED AND STILL BE COMPLIANT. |
| | 2. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN |
| | HORIZONTAL POSITION 33? MIN/36? MAXIMUM ABOVE FINISHED |
| | FLOOR TO TOP OF THE GRIPPING SURFACE, NOT TO CENTER. |
| | PER WPB FBC 107.2.1, CORRECT ?TOILET ACCESSORY |
| | SCHEDULE? ON PLAN SHT. 2.1 AND ?TYPICAL TOILET ROOM |
| | ELEVATIONS? ON PLAN SHT. 3.1. |
| | 3. PER FBC ACC 604.7, TOILET PAPER HOLDERS SHALL BE |
| | INSTALLED 7?MINIMUM/9?MAXIMUM IN FRONT OF THE WATER |
| | CLOSET. PER WPB FBC 107.2.1, CORRECT ?TOILET ACCESSORY |
| | SCHEDULE? ON PLAN SHT. 2.1 AND ?TYPICAL TOILET ROOM |
| | ELEVATIONS? ON PLAN SHT. 3.1. |
| | 4. RE: ?TYPICAL TOILET ROOM ELEVATIONS? ON PLAN SHT. |
| | 3.1. |
| | 5. WATER CLOSET SHALL BE 16?-18? FROM SIDE WALL TO |
| | CENTER PER FBC ACC 604.2. |
| | 6. REAR GRAB BAR SHALL BE 12? MINIMUM FROM CENTER OF |
| | WATER CLOSET TOWARD SIDEWALL AND 24? MINIMUM FROM |
| | CENTER OF WATER CLOSET TOWARD OPEN SIDE PER FBC ACC |
| | 604.5.2. |
| | 7. FLUSH CONTROL SHALL BE LOCATED ON OPEN SIDE OF WATER |
| | CLOSET PER FBC ACC 604.6. |
| | 8. FIXTURE SCHEDULE ON PLAN SHT. 3.1 REFERS TO TABLE |
| | 604.3 FBC 2010 AND 2010 FBC 2517.5.1.1. WEST PALM BEACH |
| | HAS ADOPTED THE 2017 FLORIDA BUILDING CODES INCLUDING |
| | PLUMBING. THE SECTIONS INDICATED DO NOT MATCH UP TO THE |
| | 2017 FBC PL. PLEASE CLARIFY PER WPB FBC 107.2.1. |
| | 10.PER WPB FBC 107. 2.1, PROVIDE A PLAN VIEW OF ALL |
| | EXISTING AND ADDED SANITARY PIPING AND WATER |
| | DISTRIBUTION. AND WATER. CLARIFY EXISTING AND ADDED. |
| | 11.SEE WASTE RISER DIAGRAM ON PLAN SHT. 3.1. |
| | A. A VENT IS REQUIRED ON THIS SYSTEM WHICH SHALL PIPE |
| | TO THE EXTERIOR OF THE BUILDING PER FBC PL 904.1. |
| | REQUIRED VENT MAY BE USED AS THE DRY VENT FOR THE |
| | SYSTEM IF SYSTEM COMPLIES WITH FBC PL |
| | B. INTERCEPTORS WITH A WATER SEAL TRAP SHALL NOT |
| | DISCHARGE DIRECTLY INTO ANOTHER TRAP (DOUBLE TRAPPED) |
| | PER FBC PL 1002.1. |
| | 12.PER WPB FBC 107. 2.1, PROVIDE PRODUCT SPECS FOR LINT |
| | INTERCEPTORS (SEE NOTE ON PLAN SHT. 3.1). |
| | 13.PER WPB FBC 107. 2.1, PROVIDE DETAIL OF WASHER |
| | CONNECTION TO INTERCEPTOR AND INTERCEPTOR DISCHARGE |
| | 14.PER WPB FBC 107. 2.1, PROVIDE PIPING DETAIL FOR |
| | TYPICAL BANK OF LINT INTERCEPTORS. INCLUDE SIZING AND |
| | VENTING |
| | 15.PROVIDE TEMPERED WATER FOR LAVATORY/LAVATORIES |
| | CONFORMING TO ASSE 1070 PER FBC PL 416.5. PROVIDE SPEC |
| | FOR SAME PER WPB FBC 107.2.1. |
| | 16.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE TWO |
| | (2) TANKLESS WATER HEATERSSHOWING PIPING AND VALVE |
| | ARRANGEMENT. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19060896 1242 PALM BEACH LAKES BLVD |
| | |