2019-07-15 10:47:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19060896
 7/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC
 AND SECTION 312.1 FBC M.
  
 2) SHEET 4.1: PLEASE CORRECT THE AHU DETAIL WHICH IS
 CITING THE FBC RESIDENTIAL CODE. THE PROPOSED PROJECT
 SHALL BE IN COMPLIANCE WITH THE FBC-17 MECHANICAL-
 SIXTH EDITION.
  
 3) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GAS DRYERS VERIFYING THE APPLIANCES IN COMPLIANCE WITH
 EITHER THE ANSI Z21.5.1 OR ANZI Z21.1.5.2 STANDARDS-
 SECTION 613.1 FBC FG.
  
 5) SHEET 4.1: SHOW THE LOCATIONS OF THE NEW GAS DRYERS
 AND PROVIDE COMPLETE VENTING PLANS. PLEASE NOTE THAT
 TYPE 2 COMMERCIAL GAS DRYER VENTING SYSTEMS SHALL BE
 ENGINEERED IN ACCORDANCE WITH MANUFACTURER'S
 SPECIFICATIONS. IF THE EXISTING SYSTEM DOES NOT MEET
 THE SPECIFICATIONS FOR THE NEW DRYERS, THAT SYSTEM
 SHALL BE ABANDONED AND A NEW SYSTEM SHALL BE INSTALLED.
 THE MECHANICAL PLANS SHALL SHOW THE INDIVIDUAL AND
 COMMON VENT LOCATIONS, SHOW THE BRANCH AND COMMON VENT
 TYPES AND VENT RUN LENGTHS AND TERMINATION LOCATION(S).
 PLEASE NOTE THAT EXHAUST FANS AND A MAKEUP AIR SYSTEM
 MAY BE REQUIRED PER THE MANUFACTURER'S SPECIFICATIONS.
 THE VENTING PLANS SHALL ALSO INDICATE THE SEQUENCE OF
 OPERATION IN ACCORDANCE WITH SECTION 614.9 FBC M WHICH
 REQUIRES CONTINUOUS FAN OPERATION OR INTERLOCKING OF OF
 INDIVIDUAL UNITS TO THE FAN.
  
 THE PLAN REVIEW IS STOPPED AT THIS TIME DUE TO LACK OF
 INFORMATION, AND DRYER AND DRYER VENTING DETAILS AND
 SPECIFICATIONS- SECTION 107.2.1 WPB.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  