| 2019-07-15 10:47:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19060896 |
| | 7/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC |
| | AND SECTION 312.1 FBC M. |
| | |
| | 2) SHEET 4.1: PLEASE CORRECT THE AHU DETAIL WHICH IS |
| | CITING THE FBC RESIDENTIAL CODE. THE PROPOSED PROJECT |
| | SHALL BE IN COMPLIANCE WITH THE FBC-17 MECHANICAL- |
| | SIXTH EDITION. |
| | |
| | 3) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 4) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | GAS DRYERS VERIFYING THE APPLIANCES IN COMPLIANCE WITH |
| | EITHER THE ANSI Z21.5.1 OR ANZI Z21.1.5.2 STANDARDS- |
| | SECTION 613.1 FBC FG. |
| | |
| | 5) SHEET 4.1: SHOW THE LOCATIONS OF THE NEW GAS DRYERS |
| | AND PROVIDE COMPLETE VENTING PLANS. PLEASE NOTE THAT |
| | TYPE 2 COMMERCIAL GAS DRYER VENTING SYSTEMS SHALL BE |
| | ENGINEERED IN ACCORDANCE WITH MANUFACTURER'S |
| | SPECIFICATIONS. IF THE EXISTING SYSTEM DOES NOT MEET |
| | THE SPECIFICATIONS FOR THE NEW DRYERS, THAT SYSTEM |
| | SHALL BE ABANDONED AND A NEW SYSTEM SHALL BE INSTALLED. |
| | THE MECHANICAL PLANS SHALL SHOW THE INDIVIDUAL AND |
| | COMMON VENT LOCATIONS, SHOW THE BRANCH AND COMMON VENT |
| | TYPES AND VENT RUN LENGTHS AND TERMINATION LOCATION(S). |
| | PLEASE NOTE THAT EXHAUST FANS AND A MAKEUP AIR SYSTEM |
| | MAY BE REQUIRED PER THE MANUFACTURER'S SPECIFICATIONS. |
| | THE VENTING PLANS SHALL ALSO INDICATE THE SEQUENCE OF |
| | OPERATION IN ACCORDANCE WITH SECTION 614.9 FBC M WHICH |
| | REQUIRES CONTINUOUS FAN OPERATION OR INTERLOCKING OF OF |
| | INDIVIDUAL UNITS TO THE FAN. |
| | |
| | THE PLAN REVIEW IS STOPPED AT THIS TIME DUE TO LACK OF |
| | INFORMATION, AND DRYER AND DRYER VENTING DETAILS AND |
| | SPECIFICATIONS- SECTION 107.2.1 WPB. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | BUILDING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |