Plan Review Notes
Plan Review Notes For Permit 19060896
Permit Number 19060896
Review Stop G
Sequence Number 1
Notes
Date Text
2019-07-02 16:05:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 A SEPARATE GAS PERMIT IS REQUIRED
 1. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS
 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SEALED
 COMBUSTION AND DIRECT VENT SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505.
 4. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR THE
 GAS PRESSURE REGULATORS.
 5. PER WPB FBC 107.2.1, CLEARLY SHOW ON THE ISOMETRIC
 DRAWING THE LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC
 FG, SECS. 402.4.1, 402.4.2. SHOW ALL SIZING, VALVES AND
 PRESSURE REGULATORS. IDENTIFY TYPE OF MATERIAL BEING
 USED.
 6. PER WPB FBC 107.2.1, LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37). INDICATE EXISTING AND NEW.
 7. PER WPB FBC 107.2.1, CLEARLY INDICATE THE TYPE OF
 GAS (LP OR NATURAL).
 8. PER WPB FBC 107.2.1, SHOW THE DISTANCE FROM THE
 POINT OF DELIVERY, (GAS METER / MP REGULATOR TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 FBC FG SEC.402.4.1, 402.4.2. CLEARLY INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN.
 9. PER WPB FBC 107.2.1, PROVIDE SIZING OF ALL PIPING
 REFERENCING THE APPLICABLE FBC FG TABLES 402.4 (1) THRU
 402.4 (37). SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM FBC FG THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM.
 10. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 MANUAL GAS SHUTOFF VALVES.
 11. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC FG 305.1
 12. PER WPB FBC 107. 2.1, PROVIDE A PLAN VIEW OF ALL
 EXISTING AND ADDED GAS DISTRIBUTION. CLARIFY EXISTING
 AND ADDED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19060896 1242 PALM BEACH LAKES BLVD
  
  
  