2019-06-21 05:23:311) A "REVISED" GAS PLAN HAS BEEN SUBMITTED TO SHOW
 FUTURE GAS APPLIANCES AND THE BTU LOAD. THIS IS THE
 EXACT SAME DRAWING THAT WAS SUBMITTED WITH THE ORIGINAL
 PERRMIT FOR THE GENERATOR, SO WHAT WAS REVISED? THE
 PIPING, PIPE SIZES FOR THESE FUTURE APPLIANCES AND THE
 FURTHEST OUTLET ( IF IT IS LONGER THAN 30 FEET) MUST BE
 SHOWN ON THE GAS PLAN.
 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED & ALL
 PIPE SIZES.2017 FBC- RES. SEC. G 2413.1, G2412.8.
 4) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017
 FBC-FUEL GAS SEC. 410.2 (7).
 5) EACH FUTURE LINE SHALL HAVE A SHUTOFF VALVE, THE
 REGULATOR, A UNION WITHIN ONE FOOT UPSTREM OR
 DOWNSTREAM OF THE REGULATOR, AND A NIPPLE AND A HARDCAP
 INSTALLED ON THE OUTLET OF THE REGULATOR. NOTE THIS ON
 THE PLANS.
  
 NOTE** A SEPARATE GAS PERMIT WILL BE REQUIREDD FOR THE
 INSTALLATION OF THE "FUTURE " GAS APPLIANCES AND
 COMBUSTION AIR CALCULATIONS WILL BE REQURED FOR THE
 COOKTOP & DRYER.
  