| 2019-07-09 06:46:08 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | BUILDING WAS CONSTRUCTED IN 2001 UNDER THE FAIR HOUSING |
| | ACT (FHA). I WOULD RECOMMEND CONSULTING A DESIGN |
| | PROFESSIONAL FAMILIAR WITH THE FAIR HOUSING ACT |
| | REQUIREMENTS. |
| | |
| | 1) PERSON DESIGNING PLAN SHALL TAKE RESPONSIBILITY BY |
| | SIGNING PLAN. FS 471, 481, 489 |
| | |
| | 2) THIS UNIT IS A DESIGN SPEC A AND A SHOWER IS NOT |
| | PERMITTED TO BE ADJACENT TO THE TOILET AS IT WILL NOT |
| | ALLOWED FOR THE REQUIRED CLEAR FLOOR SPACE. FHA 7.44, |
| | 7.45, 7.56 |
| | |
| | 3) PROVIDE BATHROOM CABINET DETAIL SHOWING THE MAX |
| | HEIGHT PERMITTED WILL BE 34". FHA 7.52 |
| | |
| | 4) PROVIDE ON PLAN ALL REQUIRED CLEAR FLOOR SPACE |
| | SHOWING EXISTING TO REMAIN. FHA 7.4 |
| | |
| | 5) PROVIDE DETAIL OR NOTE ON PLAN THAT ALL GRAB BAR |
| | REINFORCEMENT WILL REMAIN OR BE INSTALLED TO COMPLY |
| | WITH FHA 7.58 |
| | |
| | 6) PROVIDE ON PLAN THE MIN REQUIRED 18" MEASUREMENT FOR |
| | THE TOILET WILL REMAIN. FHA 7.55 |
| | |
| | 7) SUBMIT A CONCRETE SLAB DETAIL SHOWING HOW THE SLAB |
| | CUTOUT WILL BE REPAIRED TO MAINTAIN THE STRUCTURAL |
| | INTEGRITY AND FIRE STOPPING RATING. INDICATE THE SIZE |
| | OF REINFORCING BARS TO BE USED, THE EMBEDMENT DEPTH |
| | THAT THE REBAR WILL BE DOWELED INTO THE EXISTING SLAB, |
| | HOW THE DOWELS WILL BE SET IN THE EXISTING SLAB, AND |
| | THE SPACING ON CENTER OF THE DOWELS. SHOW THE THICKNESS |
| | OF THE EXISTING SLAB & THE REPAIR. WPB AMEND. TO 2010 |
| | FBC SEC.107.2.1. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | |